sinee — 7.3Function Parameter Group of Input Terminal of F02

User Manual of EM730 Series Inverter 174 12 Multi-segment speed terminal 2 is invalid/valid.) ★: When a function has no corresponding input terminal options, it is invalid (0) by default.

14 13 12 11 Set frequency of the inverter Depending on the option (F00.04) 0 of the main frequency source A 0 0 0 1 Multi-segment speed 1 (F08.00) 0 0 1 0 Multi-segment speed 2 (F08.01) 0 0 1 1 Multi-segment speed 3 (F08.02) 0 1 0 0 Multi-segment speed 4 (F08.03) 0 1 0 1 Multi-segment speed 5 (F08.04) 0 1 1 0 Multi-segment speed 6 (F08.05) 0 1 1 1 Multi-segment speed 7 (F08.06) 1 0 0 0 Multi-segment speed 8 (F08.07) 1 0 0 1 Multi-segment speed 9 (F08.08) 1 0 1 0 Multi-segment speed 10 (F08.09) 1 0 1 1 Multi-segment speed 11 (F08.10) 1 1 0 0 Multi-segment speed 12 (F08.11) 1 1 0 1 Multi-segment speed 13 (F08.12) 1 1 1 0 Multi-segment speed 14 (F08.13) 1 1 1 1 Multi-segment speed 15 (F08.14) 14 13 12 11 Set frequency of the inverter 0 Depending on the option (F00.04) of the main frequency source A 13 Multi-segment speed terminal 3 0 0 0 1 Multi-segment speed 1 (F08.00) 0 0 1 0 Multi-segment speed 2 (F08.01) 0 0 1 1 Multi-segment speed 3 (F08.02) 0 1 0 0 Multi-segment speed 4 (F08.03) 0 1 0 1 Multi-segment speed 5 (F08.04) 0 1 1 0 Multi-segment speed 6 (F08.05) 14 Multi-segment speed terminal 4 0 1 1 1 Multi-segment speed 7 (F08.06) 1 0 0 0 Multi-segment speed 8 (F08.07) 1 0 0 1 Multi-segment speed 9 (F08.08) 1 0 1 0 Multi-segment speed 10 (F08.09) 1 0 1 1 Multi-segment speed 11 (F08.10) 1 1 0 0 Multi-segment speed 12 (F08.11) 1 1 0 1 Multi-segment speed 13 (F08.12) 1 1 1 0 Multi-segment speed 14 (F08.13) 1 1 1 1 Multi-segment speed 15 (F08.14) 15 Multi-segment PID terminal 1 The 4-segment PID setting can be performed via these two terminals, as detailed in the following table (0/1:

the current function terminal is invalid/valid). 16 15 Multi-segment PID setting 0 0 Depending on the PID setting source (F09.00) 0 1 Multi-segment PID setting 1 (F09.32) 1 0 Multi-segment PID setting 2 (F09.33) 1 1 Multi-segment PID setting 3 (F09.34) 16 15 Multi-segment PID setting 16 Multi-segment PID terminal 2 0 0 Depending on the PID setting source (F09.00) 0 1 Multi-segment PID setting 1 (F09.32) 1 0 Multi-segment PID setting 2 (F09.33) 1 1 Multi-segment PID setting 3 (F09.34) 17 Multi-segment torque terminal 1 The 4-segment torque setting can be performed via these two terminals, as detailed in the following table (0/1: the current function terminal is invalid/valid).

18 17 Multi-segment torque setting 0 0 Depending on the torque setting source option (F13.01) 0 1 Multi-segment torque 1 (F13.03) 1 0 Multi-segment torque 2 (F13.04) 1 1 Multi-segment torque 3 (F13.05) 18 17 Multi-segment torque setting 18 Multi-segment torque terminal 2 0 0 Depending on the torque setting source option (F13.01) 0 1 Multi-segment torque 1 (F13.03) 1 0 Multi-segment torque 2 (F13.04) 1 1 Multi-segment torque 3 (F13.05)