User Manual of EM730 Series Inverter 176 description. 28 Speed control/torque control switching These two terminals are used to change the current inverter control mode in conjunction with F13:00 When #28 terminal is valid, speed control and torque control can be switched; and when #29 terminal is valid, only speed control is enabled. See the F13.00 description. 29 Torque control prohibition 30 Motor 1/Motor 2 switching This terminal is used to determine the current valid motor in conjunction with F00.28. If #30 terminal is valid, the motors will be switched based on the F00.28 setting. See the F00.28 description.
31 Resetting of simple PLC status (running from the first segment, with the running time cleared) When this terminal is valid, the simple PLC module will restart running from the first segment. To further understand this function, you can view the simple PLC description of the F08 group. 32 simple PLC time pause (keep running at current segment) When this terminal is valid, the simple PLC module will keep running at the current segment. When this terminal is invalid, the simple PLC module will continue to run after running at the current segment. 33 Reserved 34 counter input (≤250Hz) It is a pulse input terminal that has the counting function.
The input pulse frequency is limited to 250Hz or below, and only one terminal can be set with this function. See the description of the function codes F16.03 to F16.04. 35 High-speed count input (≤100kHz, only valid for X5) It is a pulse input terminal that has the counting function. The input pulse frequency is limited to 100kHz or below. This is valid only for the terminal X5 (that is, only F02.06=35 can be set). See the description of the function codes F16.03 to F16.04. 36 Count clearing This terminal is used to clear the counter that has a counting function.
37 Length counter input (≤250Hz) This is the pulse input terminal that has a length counting function, the input pulse frequency is limited to 250Hz or below, and only one terminal can be set with this function. See the description of the function codes F16.01 to F16.02. 38 High-speed length count input (≤100kHz, only valid for X5) This is the pulse input terminal that has a length counting function, and the input pulse frequency is limited to 100kHz or below. It is invalid only for the terminal X5 (that is, only F02.06=38 can be set). See the description of the function codes F16.01 to F16.02. 39 Length clearing This length clearing terminal has a length counting function.
40 Pulse input (≤100 kHz, only valid for This is a pulse signal input terminal, and the input pulse frequency is limited to 100kHz or below. It is valid only for the