User Manual of EM730 Series Inverter 1. In order to meet the needs of different instruments or external devices, the full-scale voltage of M1 is actually 10.9V and the full-scale current is actually 22mA. 2. The default setting of M1 is 0.00-10.00V. 3. Where there are high precision requirements for the analog output during operation, test the no-load outputs of the terminals M1 with a multimeter first. When the output functions of Y1 and R1 are set to “47: PLC output”, the output result will be controlled by the corresponding bit of F03.31. 0 indicates no output and 1 indicates that there is output.
The output type of M1 is controlled by F03.34, and the corresponding short-circuit cap of the control panel M1 needs to be set correctly according to the output voltage or current: F03.34=0: output voltage 0~10V F03.34=1: output current 4~20mA 7.5 Start/Stop Control Parameter Group of F04 Group F03.34=2: output current 0~20mA F04.00=0: direct start when F04.04=0) and pre-excitation (not suitable when F04.07=0). The starting frequency will The inverter is started at the starting frequency, following the DC braking (not suitable change to the set frequency after the holding time.
197 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F03.31 Control logic options of PLC output terminal D7 D6 D5 D4 D3 D2 D1 D0 00 000 ● 0x031F * * * * * R1 * Y1 0: no output 1: output Function code Function code name Parameter description Unit Default setting Attribute Mailing address F03.34 Output type options of analog output M1 0: 0~10V 1: 4~20mA 2: 0~20mA 0 〇 0x0322 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F04.00 Start-up method 0: direct start 1: start of speed tracking 0 〇 0x0400