sinee — 7.14Torque Control Parameter Group of F13 Group

User Manual of EM730 Series Inverter The motor speed can be changed gently by setting the acceleration and deceleration time of torque control. or fall from the rated current to 0. F13.06 represents the time for the torque current to rise from 0 to the rated torque current F13.08=0: depending on F13.09 The upper frequency limit depends on F13.09 during torque control. F13.08=1:AI1 F13.08=2:AI2 The upper frequency limit in torque control is AI (percentage) * F13.09. meaning. 100.00% is the percentage to the set value of F13.09 (upper frequency limit of torque For the details of AI1 and AI2, refer to the F00.04 description. They have the same control). F13.08=5:

High-frequency pulse input (X5) The upper frequency limit in torque control is HDI (percentage) * F13.09. For the details of AI1-AI2 and X5, refer to the F00.04 description. They have the same 268 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F13.08 Upper frequency limit options of torque control 0: set by F13.09 1: AI1 2: AI2 3: reserved 4: reserved 5: high frequency pulse input (X5) 6: communication percentage setting 7:

direct communication setting 0 〇 0x0D08 F13.09 Upper frequency limit of torque control 0.50 to maximum frequency F00.16 Hz 50.00 ● 0x0D09 F13.10 Upper frequency limit offset 0.00 to maximum frequency F00.16 Hz 0.00 ● 0x0D0A F13.18 Reverse speed limit options 0 ~ 100 % 100 ● 0x0D12 F13.19 Speed priority enabling of torque control 0: disable 1: enable 1 ● 0x0D13