sinee — 6.2.5 Frequency command limit

User Manual of EM760 High-Performance Inverter F00.08=2: the larger of main and auxiliary operation results The main and auxiliary operation result is the larger of the two items, and may be positive or negative. That is, the result of the forward 20.00Hz and reverse 40.00Hz is forward 20.00Hz. F00.08=3: the smaller of main and auxiliary operation results The main and auxiliary operation result is the smaller of the two items, and may be positive or negative. That is, the result of the forward 20.00Hz and reverse 40.00Hz is reverse 40.00Hz. F00.08=4:

main frequency source A - auxiliary frequency source B, and the result is greater than or equal to zero The main and auxiliary operation result is the difference of the two items, and is greater than or equal to zero, that is, the result of the forward 20.00Hz and reverse 40.00Hz is running at 0Hz. F00.08=5: main frequency source A + auxiliary frequency source B, and the result is greater than or equal to zero The main and auxiliary operation result is the sum of the two items, and is greater than or equal to zero, that is, the result of the forward 20.00Hz and reverse 40.00Hz is running at 0Hz (the upper frequency limit is F00.18).

During the main and auxiliary operations, the range of the auxiliary frequency source B depends on the selected object, maximum frequency by default. If selected as relative to the main frequency source A (F00.09=1), the range ofthe auxiliary frequency source B will change along with that ofthe main frequency source A. 6.2.5 Frequency command limit The allowable maximum frequency of the inverter is represented by Fmax. The Fmax range is from 20.00 to 600.00Hz. When the frequency resolution F00.31=1 (resolution is 0.1 Hz), the maximum frequency settable is 3,000.0 Hz.

105 Function code Function codename Parameter description Unit Default setting Attribute F00.09 Reference options of auxiliary frequency source B in main and auxiliary operation 0: relative to the maximum frequency 1: Relative to main frequency source A 0 〇 Function code Function code name Parameter description Unit Default setting Attribute F00.16 Maximum frequency 1.00~600.00 Hz 50.00 〇 Function code Function codename Parameter description Unit Default setting Attribute F00.17 Options of upper frequency limit control 0: set by F00.18 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: percent setting of upper limit frequency communication 7:

direct setting of upper limit frequency communication 0 〇