sinee — 6.4.1 Start-up method

User Manual of EM760 High-Performance Inverter * DC braking is started as shown in the figure below. Fig. 6-13 Process of starting DC braking When multiple motors are driven by a single inverter, this function can be applied. The inverter will start running after the magnetic field is established according to the set pre- excitation current F04.06 and the set pre-excitation time F04.07 is up. Ifthe pre-excitation time is set to 0, the inverter will be started directly without pre-excitation. The pre-excitation current F04.06 is the percentage relative to the rated no-load current of the motor.

112 Function code Function codename Parameter description Unit Default setting Attribute F04.06 Pre-excitation current 50.0-500.0 (100.0 = no-load current) % 100.0 〇 F04.07 Pre-excitation time 0.00~10.00 s 0.10 〇 Function code Function code name Parameter description Unit Default setting Attribute F04.08 Speed tracking mode Ones place: Tracking start frequency 0: maximum frequency 1: stop frequency 2: power frequency Tens place: Selection of search direction 0: search only in command direction 1: Search in the opposite direction if the speed cannot be found in the command direction 01 〇