sinee — 6.5.1 Digital input terminal (DI)

User Manual of EM760 High-Performance Inverter Fig. 6-18 Schematic Diagram of Positive/Negative Logic Sampling of Terminal When the bit is set to 0, the multi-function input terminal is valid in the closed status and invalid in the open status; When the bit is set to 1, the multi-function input terminal is valid in the open status and invalid in the closed status. These function code are subject tobit operation. You only need to set the corresponding bit to 0 or 1. Take F02.15 as an example, as shown in the following table: Table 6-13 Function Code Details of Bit Operation The seventh bit is reserved and cannot be set. The specific displayed value does not mean anything. For example:

To set the terminal X1 to reverse logic, you only need to set the 0 th bit corresponding to X1 to 1, i.e. F02.15=xxxxxxx1. To set the terminals X1 and X5 to reverse logic, you only need to set the 0 th bit corresponding to X1 and 4 th bit corresponding to X5 to 1. That is, 02.15=xxx 1xxx1. * This function is for logic matching with other external devices. 127 Setting item * X7 X6 X5 X4 X3 X2 X1 Corresponding bit * 6 5 4 3 2 1 0 Settings * 0/1 0/1 0/1 0/1 0/1 0/1 0/1 Function code Function codename Parameter description Unit Default setting Attribute F02.17 Filtering times of digital input terminal 0 - 10,000; 0: no filtering; n: sampling once in nms 2 〇