sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 311 3: Automatic switching by frequency F09.12 PID parameter switching deviation 1 0.00~F09.13 % 20.00 ● 0x090C F09.13 PID parameter switching deviation 2 F09.12~100.00 % 80.00 ● 0x090D F09.14 Initial PID value 0.00~100.00 % 0.00 ● 0x090E F09.15 PID initial value holding time 0.00~650.00 s 0.00 ● 0x090F F09.16 Upper limit of PID output F09.17~+100.0 % 100.0 ● 0x0910 F09.17 Lower limit of PID output –100.0~F09.16 % 0.0 ● 0x0911 F09.18 PID deviation limit 0.00-100.00 (0.00:

invalid) % 0.00 ● 0x0912 F09.19 PID differential limit 0.00~100.00 % 5.00 ● 0x0913 F09.20 PID integral separation threshold 0.00-100.00 (100.00% = invalid integral separation) % 100.00 ● 0x0914 F09.21 PID setting change time 0.000~30.000 s 0.000 ● 0x0915 F09.22 PID feedback filtering time 0.000~30.000 s 0.000 ● 0x0916 F09.23 PID output filtering time 0.000~30.000 s 0.000 ● 0x0917 F09.24 Upper limit detection value of PID feedback disconnection 0.00-100.00; 100.00 = invalid feedback disconnection % 100.00 ● 0x0918 F09.25 Lower limit detection value of PID feedback disconnection 0.00-100.00; 0.00 = invalid feedback disconnection % 0.00 ● 0x0919 F09.26 Detection time of PID feedback disconnection 0.000~30.000 s 0.000 ● 0x091A F09.27 PID sleep control options 0:

Invalid 1: sleep at zero speed 2: sleep at lower frequency limit 3: sleep with tube sealed 0 ● 0x091B