User Manual of EM760 High-Performance Inverter F09.00=1: AI1 F09.00=2: AI2 F09.00=3: AI3 F09.00=4: AI4 See 6.5.7 for details ofAI1 to AI4. When serving as PID setting, the percentage is directly given, and the maximum output is 100.00%. F09.00=5: PULSE, high-frequency pulse (X7) The set percentage of PID is directly dependent on the HDI (percentage). See 6.5.3 for details of X7 serving as high-speed pulse input. When serving as PID setting, the percentage is directly given, and the maximum output is 100.00%. F09.00=6: communication setting The percentage of PID setting depends directly on the communication (percentage).
● If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific feedback percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%. ● For the general communication (F10.05=0), the specific setting percentage is “7004H (communication setting of process PID setting)”, and the 7004H data range is -100.00% to 100.00%. F09.02=1: AI1 F09.02=2: AI2 F09.02=3: AI3 F09.02=4: AI4 The PID feedback percentage is directly dependent on the AI (percentage). See 6.5.7 for details of AI1 to AI4.
When serving as PID feedback, the percentage is directly given, and the maximum output is 100.00%. F09.02=5: PULSE, high-frequency pulse (X7) 88 Function code Function codename Parameter description Unit Default setting Attribute F09.02 PID feedback source 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: PULSE, high-frequency pulse (X7) 6: Communication setting 1 〇