sinee — 6.2.3.1 Setting auxiliar

User Manual of EM760 High-Performance Inverter PID settings are determined in conjunction with the setting of the function code F09.00. The EM760 series inverter has a multi-segment PID setting function, and its switching conditions are mainly dependent on the input functions “15: multi-segment PID terminal 1” and “16: multi-segment PID terminal 2”, as detailed in the table below. Table 6-8 Details of Multi-segment PID Setting Function The upper and lower limits of the feedback voltage can be used for automatic material cutoff detection in winding applications. They represent the upper and lower limits of material cutoff, respectively.

Due to the particularity of winding applications, F09.35 and F09.36 can be used to reflect the real sensor boundaries, which is more conducive to the system stability.

96 Function code Function codename Parameter description Unit Default setting Attribute F09.32 Multi-segment PID setting 1 0.0 to PID setting feedback range F09.03 0.0 ● F09.33 Multi-segment PID setting 2 0.0 to PID setting feedback range F09.03 0.0 ● F09.34 Multi-segment PID setting 3 0.0 to PID setting feedback range F09.03 0.0 ● Method Setting Scope PID Setting 16 15 F09.00 Invalid Invalid 0 F09.01 0.0~F09.03 0.00%~100.00% 1 AI1 -100.00%~100.00% -100.00%~100.00% 2 AI2 -100.00%~100.00% -100.00%~100.00% 6 485 -100.00%~100.00% -100.00%~100.00% Invalid Valid -- F09.32 0.0~F09.03 0.00%~100.00% Valid Invalid -- F09.33 0.0~F09.03 0.00%~100.00% Valid Valid -- F09.34 0.0~F09.03 0.00%~100.00% Function code Function codename Parameter description Unit Default setting Attribute F09.35 Upper limit of feedback voltage Lower limit of feedback voltage to 10.00 V 10.00 ● F09.36 Lower limit of feedback voltage 0.00 to upper limit of feedback voltage V 0.00 ● Function code Function codename Parameter description Unit Default setting Attribute F09.37 Options of integral action within the set change time of PID 0:

Always calculate the integral term 1: Calculate the integral term after the F09.21 set time is reached 2: Calculate the integral term when the error is less than F09.38 0 ● F09.38 Input deviation of integral action within the set change time of PID 0.00~100.00 % 30.00 ●