4-2 Function Mode „ Specifications of Multi-function Output Terminals P1, P2 •Below are the specifications of multi-function output terminals P1, P2. Inverter's internal circuitry Electrical specifications Between each terminal and PC Voltage drop 4 V max. at power-on Max. allowable voltage: 27 V DC Max. allowable current: 50 mA 4 Functions •Connect multi-function output terminals P1 and P2 at the same sink/source logics. •The PC terminal acts as a common terminal at sink/source logics. „ Relay Output Contact Selection •The relay output terminal has an SPDT contact configuration. Below is the operation.
Electrical specifications MB MA MC Inverter's internal circuitry (a) When used as an alarm terminal (b) When used as an output terminal 4-61 P2 PC P1 031 to C032 set values Power supply Output status 00 (NO contact) ON ON OFF OFF 01 (NC contact) ON ON OFF OFF Output terminal Resistance load Inductive load MA-MC Max. contact capacity 250 V AC, 2 A 30 V DC, 3 A 250 V AC, 0.2 A 30 V DC, 0.6 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA MB-MC Max. contact capacity 250 V AC, 1 A 30 V DC, 1 A 250 V AC, 0.2 A 30 V DC, 0.2 A Min.
contact capacity 100 V AC, 10 mA 5 V DC, 100 mA C036 set value Powe supply r Inverter status Output terminal status MA-MC MB-MC 00 ON Abnormal Normal Closed Open Open Closed OFF Open Closed 01 ON Abnormal Normal Open Closed Closed Open OFF Open Closed C036 set value Power supply Output signal Output terminal status MA-MC MB-MC 00 ON ON Closed Open OFF Open Closed OFF Open Closed 01 ON ON Open Closed OFF Closed Open OFF Open Closed