omron — Extended Function Mode

Appendix-1 Parameter List * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. Appendix App-7 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value PID control A071 PID selection 00: Disabled 01: Enabled 00 No  A072 PID P gain 0.2 to 5.0 1.0 Yes  A073 PID I gain 0.0 to 150.0 1.0 Yes s A074 PID D gain 0.00 to 100.0 0.0 Yes s A075 PID scale 0.01 to 99.99 1.00 No Time A076 PID feedback selection 00: FI 01: FV 02: RS485 communication 10: Operation function output 00 No  A077 Reverse PID function 00: OFF (Deviation = Target value - Feedback value) 01:

ON (Deviation = Feedback value - Target value) 00 No  A078 PID output limit function 0.00 to 100.0 0.0 No % AVR A081 AVR selection 00: Always ON 01: Always OFF 02: OFF during deceleration 02 No  A082 AVR voltage selection 200-V class: 200/215/220/230/240 400-V class: 380/400/415/440/460/480 200/ 400 No V