omron — Frequency Addition Function

4-2 Function Mode Operation Frequency Function •Two systems of frequency reference operation results are available for the frequency reference and PID feedback value. 4 Functions Note 1: When this function is enabled, the Up/Down function cannot be used. In addition, frequency cannot be changed through key operations from output frequency monitor d001, frequency conversion monitor d007, or output frequency setting F001. Note 2: The same setting is available in A141 and A142. •To use this function as a frequency reference, set frequency reference selection A001 to "10". •To use this function as a PID feedback, set PID feedback selection A076 to "10".

Frequency Addition Function •The value set in frequency addition amount A145 can be added to or subtracted from the selected frequency reference value. •To use this function, allocate 50 (ADD) to any of the multi-function inputs. The A145 value is added or subtracted with the ADD terminal turned on. Note 1: If the sign of the frequency reference is changed ((-) → (+), or (+) → (-)) as a result of operation, the rotation direction will be inverted. Note 2: When the PID function is used, the frequency addition function is enabled for a PID target value. (Note that A145 is displayed in % (in increments of 0.01%).) 4-41 Parameter No.

Function name Data Default setting Unit A141 Operation frequency input A setting 00: Digital Operator (F001) (A020/A220/A320) 01: Digital Operator (FREQ adjuster) (Enabled when 3G3AX-OP01 is used.) 02: Input FV 03: Input FI 04: RS485 communication 05: Option 1 06: Option 2 07: Pulse train frequency 02  A142 Operation frequency input B setting 03  A143 Operator selection 00: Addition (A + B) 01: Subtraction (A - B) 02: Multiplication (A × B) 00  Related functions A001 = 10, A076 = 10 Parameter No. Function name Data Default setting Unit A145 Frequency addition amount 0.0 to 400.0 0.00 Hz A146 Frequency addition direction 00: Add A145 value to output frequency 01:

Subtract A145 value from output frequency 00  Related functions C001 to C008, ADD input