omron — 2nd/3rd Control Function

4-2 Function Mode *1. When the emergency shutoff function is enabled (SW1 = ON), C001 and C003 are forced to change to "18" (RS) and "64" (EMR), respectively. (You cannot intentionally set "64".) If SW1 is turned on and then off, C003 is set to "no" (no allocation). The functions switchable via the SET/SET3 terminal are: F002/F202/F302 * : 1st/2nd/3rd acceleration time F003/F203/F303 * : 1st/2nd/3rd deceleration time A003/A203/A303 : 1st/2nd/3rd base frequency A004/A204/A304 : 1st/2nd/3rd maximum frequency A020/A220/A320 * : 1st/2nd/3rd multi-step speed reference 0 A041/A241 : 1st/2nd torque boost selection A042/A242/A342 * : 1st/2nd/3rd manual torque boost voltage A043/A243/A343 * :

1st/2nd/3rd manual torque boost frequency A044/A244/A344 : 1st/2nd/3rd V/f characteristics selection A046/A246 * : 1st/2nd automatic torque boost voltage compensation gain A047/A247 * : 1st/2nd automatic torque boost slip compensation gain A061/A261 * : 1st/2nd frequency upper limit A062/A262 * : 1st/2nd frequency lower limit A092/A292/A392 * : 1st/2nd/3rd acceleration time 2 A093/A293/A393 * : 1st/2nd/3rd deceleration time 2 A094/A294 : 1st/2nd 2-step acceleration/deceleration selection A095/A295 : 1st/2nd 2-step acceleration frequency A096/A296 : 1st/2nd 2-step deceleration frequency b012/b212/b312 * : 1st/2nd/3rd electronic thermal level b013/b213/b313 * :

1st/2nd/3rd electronic thermal characteristics selection H002/H202 : 1st/2nd motor parameter selection H003/H203 : 1st/2nd motor capacity selection H004/H204 : 1st/2nd motor pole number selection H005/H205 * : 1st/2nd speed response H006/H206/H306 * : 1st/2nd/3rd stabilization parameter H020/H220 : 1st/2nd motor parameter R1 H021/H221 : 1st/2nd motor parameter R2 H022/H222 : 1st/2nd motor parameter L H023/H223 : 1st/2nd motor parameter I0 H024/H224 : 1st/2nd motor parameter J H030/H230 : 1st/2nd motor parameter R1 (auto-tuning) H031/H231 : 1st/2nd motor parameter R2 (auto-tuning) H032/H232 : 1st/2nd motor parameter L (auto-tuning) H033/H233 :

1st/2nd motor parameter I0 (auto-tuning) H034/H234 : 1st/2nd motor parameter J (auto-tuning) H050/H250 * : 1st/2nd PI proportional gain H051/H251 * : 1st/2nd PI integral gain H052/H252 * : 1st/2nd P proportional gain H060/H260 * : 1st/2nd Limit at 0 Hz 4 Functions *: Parameters changeable during operation. • The 1st/2nd/3rd control functions are displayed identically. You'll see which one is enabled by checking whether the terminal is turned on/off. • When both SET and SET3 terminals are turned on, priority is given to SET, and the 2nd control function is enabled. • During operation, you cannot switch between the 1st, 2nd, and 3rd control functions. You can switch them only during stop.

4-80 U/T1 V/T2 W/T3 Inverter SET SET3 CM1 Motor 1 Motor 2 Motor 3