4-4 Communication Function Reads the Inverter status. •Transmission frame Frame format 4 Functions •Response frame Frame format * Inverter status data includes the following three elements (A, B, and C). Data 4-145 STX Station No. Command BCC CR Description Data size Setting STX Control code (Start of TeXt) 1 byte STX (0x02) Station No. Station No. of the target Inverter 2 bytes 01 to 32 Command Transmission command 2 bytes 04 BCC Block check code 2 bytes Exclusive OR from station No. to data. (Refer to page 4-153.) CR Control code (Carriage Return) 1 byte CR (0x0D) STX Station No. Data BCC CR Description Data size Setting STX Control code (Start of TeXt) 1 byte STX (0x02) Station No.
Station No. of the target Inverter 2 bytes 01 to 32 Data Data 8 bytes * BCC Block check code 2 bytes Exclusive OR from station No. to data. (Refer to page 4-153.) CR Control code (Carriage Return) 1 byte CR (0x0D) Status A Status B Status C 00 (Reserved)