4-4 Communication Function 4 Functions 4-186 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1334h Selection of non-stop function at momentary power interruption b050 R/W 0: Disabled 1: Deceleration stop 2: Momentary power interruption non- stop (without recovery) 3:
Momentary power interruption non- stop (with recovery) 1335h Starting voltage of non-stop function at momentary power interruption b051 R/W 0 to 10000 0.1 [V] 1336h Starting deceleration level of non-stop function at momentary power interruption b052 R/W 0 to 10000 0.1 [V] 1337h Deceleration time of non-stop function at momentary power interruption b053 (HIGH) R/W 0 to 360000 0.01 [s] 1338h b053 (LOW) R/W 1339h Deceleration starting width of non-stop function at momentary power interruption b054 R/W 0 to 1000 0.01 [Hz] 133Ah Proportional gain setting of non-stop function at momentary power interruption b055 R/W 0 to 255 0.01 133Bh Integral time setting of non-stop function at momentary power interruption b056 R/W 0 to 65535 0.001 [s] 133Ch to 133Eh Not used 133Fh Window comparator FV upper limit level b060 R/W Set an upper limit level.
Setting range: 0 to 100 Lower limit: Lower limit level + Hysteresis width × 2 1 [%] 1340h Window comparator FV lower limit level b061 R/W Set a lower limit level. Setting range: 0 to 100 Upper limit: Upper limit level - Hysteresis width × 2 1 [%] 1341h Window comparator FV hysteresis width b062 R/W Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2 1 [%] 1342h Window comparator FI upper limit level b063 R/W Set an upper limit level. Setting range: 0 to 100 Lower limit: Lower limit level + Hysteresis width × 2 1 [%]