omron — Modbus-RTU Method

4-4 Communication Function * Data on H003 (motor capacity selection) is the following code data. 4 Functions 4-205 Code data 00 01 02 03 04 05 06 07 08 09 10 Motor capacity (kW) 0.2  0.4  0.75  1.5 2.2  3.7  Code data 11 12 13 14 15 16 17 18 19 20 21 Motor capacity (kW) 5.5 7.5 11 15 18.5 22 30 37 45 55 75 Register No. Function name Function code R/W Monitor and setting parameters Resolution 2103h 2nd acceleration time 1 F202 (HIGH) R/W 1 to 360000 0.01 [s] 2104h F202 (LOW) R/W 2105h 2nd deceleration time 1 F203 (HIGH) R/W 1 to 360000 0.01 [s] 2106h F203 (LOW) R/W 2107h to 2202h Not used    Register No.

Function name Function code R/W Monitor and setting parameters Resolution 2203h 2nd base frequency A203 R/W 30 to 2nd max. frequency 1 [Hz] 2204h 2nd max. frequency A204 R/W 30 to 400 1 [Hz] 2205h to 2215h Not used    2216h 2nd multi-step speed reference 0 A220 (HIGH) R/W 0, Starting frequency to 2nd max. frequency 0.01 [Hz] 2217h A220 (LOW) R/W 2218h to 223Ah Not used    223Bh 2nd torque boost selection A241 R/W 0: Manual torque boost 1: Automatic torque boost  223Ch 2nd manual torque boost voltage A242 R/W 0 to 200 0.1 [%] 223Dh 2nd manual torque boost frequency A243 R/W 0 to 500 0.1 [%] 223Eh 2nd V/f characteristics selection A244 R/W 0: VC 1: Special VP 2: Free V/f 3:

Sensorless vector 4: 0-Hz sensorless vector 