5-2 Warning Function 5-2 Warning Function •The following table shows the details of warning display and parameter correction. 5 Maintenance Operations *1. In this case, the base frequency is rewritten when correcting parameters. Change the data to a correct value if a warning occurs. Otherwise, the motor may burn out depending on the value. *2. Checks even if the frequency reference selection (A001) is set other than to the Digital Operator (02). *3. The jump frequency is rewritten into the value of the subtraction of the jump width (lower limit) from the jump frequency.
5-10 Warning display Target code Condition Base code 001/201 Frequency upper limit A061/A261 > Maximum frequency A004/A204/A304 002/202 Frequency lower limit A062/A262 > 004/204/304 Base frequency A003/A203/A303 *1 > 005/205/305 Output frequency F001, Multi-step speed reference 0 A020/ A220/A320 *2 > 006/206/306 Multi-step speeds 1 to 15 A021 to A035 > 009 Orientation speed setting P015 > 012/212 Frequency lower limit A062/A262 > Frequency upper limit A061/A261 015/215 Output frequency F001, Multi-step speed reference 0 A020/ A220 *2 > 016/216 Multi-step speeds 1 to 15 A021 to A035 > 019 Frequency upper limit A061/A261 Orientation speed P015 021/221 Frequency lower limit A062/A262 025/225 Output frequency F001, Multi-step speed reference 0 A020/ A220/A320 *2 031/231 Frequency upper limit A061/A261 Starting frequency b082 032/232 Frequency lower limit A062/A262 035/235/335 Output frequency F001, Multi-step speed reference 0 A020/ A220/A320 *2 036 Multi-step speeds 1 to 15 A021 to A035 037 Jogging frequency A038 085/285/385 Output frequency F001, Multi-step speed reference 0 A020/ A220/A320 *2 Jump frequency 1/2/3 ± Jump width A063 ± A064 A065 ± A066 A067 ± A068 *3 086 Multi-step speeds 1 to 15 A021 to A035