ENGLISH Thank you for choosing Delta’s DVP series PLC. The analog input module of DVP04AD-SL series can read/write the data of analog input module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog input signal either in voltage or in current. Users can select input from voltage or current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5μV). Current input range is -20mA ~ 20mA (resolution is 625nA). EN DVP04AD-SL is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration.

To prevent non-maintenance staff from operating DVP04AD-SL, or to prevent an accident from damaging DVP04AD-SL, the control cabinet in which DVP04AD-SL is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04AD-SL is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP04AD-SL is powered up. After DVP04AD-SL is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP04AD-SL is correctly grounded in order to prevent electromagnetic interference. FR DVP04AD-SL est un module OUVERT.

Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP04AD-SL pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP04AD-SL. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante.

Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. Product Profile & Dimension 6 7 8 63.4 [2.496] 9 5 10 60 [2.362] 33.1 [1.303] 5 [ Figure 1 ] Unit: mm [inch] 1. I/O module connection port 6. Mounting hole of the I/O module 2. Status indicator (POWER, RUN and ERROR) 7. I/O module connection port 3. Model name 8. Mounting slot (35mm) 4. I/O terminals 9. I/O module clip 5. Mounting slot clip 10. DC power input - 1 - 1 2 [3.543] 90 3 3 [0.118] 4 AD

Стр. 2

I/O Terminal Layout CH1 Ch2 Ch3 Ch4 External Wiring DVP04AD-SL (4AI) Active-type Passive-type U IN + Voltage input CH1 250 V1+ I1+ VI1- 1M AG CH1 - Shielded cable*1 *5 FE 1M Current input CH4 *2 CH4 V4+ 1M AG Shielded cable*1 Terminal of power module + 1M - I4+ VI4- FE 250 *4 *3 DC/DC +15V Grounding (100 or less) System grounding 0V 24V Converter -15V AG [ Figure 3 ] Note 1: When performing analog input, please isolate other power wirings. Note 2: When the A/D module is connected to current signals, make sure you short-circuit “V+” and “I+” terminals. Note 3: If the noise is too significant, please connect FE to the grounding terminal. Note 4:

Please connect the terminal on both the power module and A/D module to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet. Note 5: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor.

Electrical Specifications - 2 - V1+ I1+ V1- FG V2 + I2+ V2- FG V3+ I3+ V 3- FG V4+ I4+ V4- FG AG Voltage input CH1 1M UIN + *5 V VI11 I+ 1+ 250 1M - - Shielded cable*1 FE AG Current input CH4 1M UIN + *2 V VI44 I+ 4+ 250 1M - - Shielded cable*1 FE *3 Terminal of power module *4 0V DC/DC +15V System 24V Converter AG grounding -15V Grounding (100 or less) CH1 CH4 [ Figure 2 ] Analog / Digital module Voltage input Current input 24VDC (-15% ~ +20%) / 3.5W DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A) Power supply voltage

Стр. 3

Control Register - 3 - Analog / Digital module Voltage input Current input Analog input channel 4 channels / each module Range of analog input ±10V ±5V ±20mA 0 ~ 20mA 4 ~ 20mA Range of digital ±32,000 ±32,000 ±32,000 0 ~ 32,000 0 ~ 32,000 conversion Hardware Resolution 16 bits 16 bits 16 bits 15 bits 15 bits Input impedance 0.3% when in full scale (25°C, 77°F)  0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F) Overall accuracy Response time 250μs / each channel Max. output current 1KΩ ~ 2MΩ - Tolerance carried - 0Ω~500Ω impedance Digital data format 2’s complement of 16 bits, 15 significant bits Optical coupler isolation between digital circuits and analog circuits.

No isolation among analog channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground Isolation method Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU. Series connection to DVP-PLC MPU Operation/storage Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity) temperature Vibration/shock International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) immunity CR# Attrib.

Register name Explanation #0 O R Model name Set up by the system: DVP04AD-SL model code = H’4400 #1 O R Firmware version Display the current firmware version in hex. #2 X R/W CH1 input mode setting Input mode: Default = H’0000. Take CH1 for example: Mode 0 (H’0000): Voltage input (±10V) Mode 1 (H’0001): Current input (±20mA) Mode 2 (H’0002): Current input (0~+20mA) Mode 3 (H’0003): Current input (+4~+20mA) Mode 4 (H’0004): Voltage input (±5V) Mode 5 (H’0005): Voltage input (0V~+5V) Mode 6 (H’0006): Voltage input (1V~+5V) Mode -1 (H’FFFF):

Channel 1 unavailable #3 X R/W CH2 input mode setting #4 X R/W CH3 input mode setting #5 X R/W CH4 input mode setting #6 X R/W History mode b15 ~ b12 b11 ~ b8 b7 ~ b4 b3 ~ b0 CH4 CH3 CH2 CH1 Only average values are recorded. Default = H’0000. Take CH1 for example: K0: Disable (Default). K1: Single. K2: Auto. K3: Rising Edge Triggered K4: Falling Edge Triggered #7 X R/W History command Refer to table of history command for detail. Default = H’0000 #8 X R/W CH1 sampling range Set sampling range in CH1 ~ CH4: Range = K1 ~ K20 Default = K10 #9 X R/W CH2 sampling range #10 X R/W CH3 sampling range #11 X R/W CH4 sampling range