CANopen Slave Communication Module IFD9503 5. Note: The changed values on SW1 or SW2 are only valid when IFD9503 is re-powered. When IFD9503 is operating, changing the set value of node address will be invalid. 2.4 Function Setup DIP switch The DIP switch SW3 is to be used on the equipment connected to IFD9503, SW3 DIP ON the selection of communication ports and setting up the baud rate of IFD9503 and the master in CANopen. 1 2 3 4 5 6 7 8 1. Selecting equipment connected to IFD9503 z Example If the equipment connected to IFD9503 is Delta servo drive, you only need to switch PIN 3 in SW3 to “On”, PIN 1 and PIN 2 to “Off” and re-power IFD9503. z Note:

The changed setting of DIP switch is only valid when IFD9503 is re-powered. When IFD9503 is operating, changing the setting of DIP switch will be invalid. 2. Selecting IFD9503 communication mode z Note: The changed setting of the communication mode is only valid when IFD9503 is re-powered. When IFD9503 is operating, changing the setting of communication mode will be invalid. 3.

Setting up baud rate DVP-PLC Application Manual 6 Address setting Description 0 ~ 7F Valid CANopen node address 80 ~ FF Invalid CANopen node address PIN 3 PIN 2 PIN 1 Equipment Off Off On AC motor drive Off On Off Programmable logic controller Off On On Temperature controller On Off Off Servo drive On Off On Human machine interface On On Off Custom equipment On On On Test mode PIN 5 PIN 4 Communication mode Off Off RS-485 On On RS-232 Off On Incorrect setting On Off PIN 8 PIN 7 PIN 6 Baud rate Off Off Off 10k bps Off Off On 20k bps