Delta Electronics — 2.6.1 EMI filters

Installation ASDA-B3 Motor cable selection and installation precautions The selection of motor cable (refer to Appendix B Accessories) and installation accuracy 2 determine the performance of the EMI filter. Follow these precautions: 1. Use a cable that has braided shielding (the effect of double shielding is better). 2. The shield on both ends of the motor cable should be grounded with the shortest cable length and the largest contact area. 3. Remove the protective paint on the U-shape saddle and metal plate to ensure good contact. See the following figure. 4. Correctly connect the braided shielding of the motor cable and the metal plate:

fix the braided shielding on both ends of the motor cable with the U-shape saddle and metal plate. See the following figure. (1) (2) (3) (1) Remove the protective paint on the U-shape saddle and metal plate to ensure good contact. (2) U-shape saddle (3) Well-grounded metal plate 2-16