ENGLISH Thank you for choosing DELTA DVP PLC Series. The analog output module of DVP04DA-SL series can read/write the data of analog output module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog output module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog output signal either in voltage or in current. Users can select output from voltage or current via wiring. Voltage output range is -10V~10VDC (resolution is 312.5 μ V). Current output range is 0mA ~ 20mA (resolution is 625nA). EN DVP04DA-SL is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration.

To prevent non-maintenance staff from operating DVP04DA-SL, or to prevent an accident from damaging DVP04DA-SL, the control cabinet in which DVP04DA-SL is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04DA-SL is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP04DA-SL is powered up. After DVP04DA-SL is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP04DA-SL is correctly grounded in order to prevent electromagnetic interference. FR DVP04DA-SL est un module OUVERT.

Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP04DA-SL pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP04DA-SL. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante.

Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. Product Profile & Dimension 6 7 8 63.4 [2.496] 9 5 10 60 [2.362] 33.1 [1.303] 5 [ Figure 1 ] Unit: mm [inch] 1. I/O module connection port 6. Mounting hole of the I/O module 2. Status indicator (POWER, RUN and ERROR) 7. I/O module connection port 3. Model name 8. Mounting slot (35mm) 4. I/O terminals 9. I/O module clip 5. Mounting slot clip 10. DC power input - 1 - 1 2 [3.543] 90 3 3 [0.118] 4 DA

Стр. 2

I/O Terminal Layout CH1 Ch2 Ch3 Ch4 External Wiring DVP04DA-SL (4AO) *2 Voltage output CH1 CH1 V+ I+ COM AC drive, recorder, scale value... Isolation wire*1 FG Current output CH4 CH4 I+ COM V+ AC drive, recorder, scale value... Isolation wire*1 FG Terminal of power module *3 DC24V 24- converter DC/DC +15V -15V AG Note 1: Please isolate analog output and other power wiring. Note 2: If noise interferes from loaded input wiring terminal is significant, please connect a capacitor with 0.1 ~ 0.47μF 25V for noise filtering. Note 3: Please connect power module terminal and analog output module terminal to system earth point and make system earth point be grounded or connects to machine cover.

Specifications Class 3 grounding (100 or less) System grounding [ Figure 2 ] - 2 - V1+ I1+ COM FG V 2+ I 2+ COM FG V 3+ I3+ COM FG V4+ I4+ COM FG 24+ Digital/Analog module Voltage output Current output 24VDC (-15% ~ +20%) / 3.5W3 DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A) Power supply voltage Analog input channel 4 channels/each module Analog output range ±10V 0 ~ 20mA 4 ~ 20mA Digital data range ±32,000 0 ~ 32,000 0 ~ 32,000 Resolution 16 bits 15 bits 15 bits Output impedance 0.3% when in full scale (25°C, 77°F)  0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F) Overall accuracy Response time 250μs / each channel Max.

output current 1kΩ ~ 2MΩ - Tolerance carried - 0Ω ~ 500Ω impedance Digital data format 2’s complementary of 16-bit, 15 significant bits Optical coupler isolation between analog circuits and digital circuits. No isolation among analog channels. 500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground Isolation method

Стр. 3

Control Register - 3 - Digital/Analog module Voltage output Current output Voltage output has short circuit protection, but a long period short circuit may cause internal wire damage and current output break. Protection Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU. Connect to DVP-PLC MPU in series Operation: 0 ~ 55°C (temp.); 50 ~ 95% (humidity); pollution degree 2 Storage: -25 ~70°C (temp.); 5 ~ 95% (humidity) Operation/storage Vibration/shock International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) immunity CR# Attrib.

Register name Explanation #0 O R Model name System used, data length is 8 bits (b7 ~ b0). Model code = H’4401. User can read the data from program to check if there is I/O module. #1 O R Firmware version Display the current firmware version in hex. For example: 1.0A means CR#1 = H’010A. #2 X R/W CH1 output mode setting Output mode: Default = H’0000. Take CH1 for example: Mode 0 (H’0000): Voltage output (10V) Mode 1 (H’0001): Current output (0~+20mA) Mode 2 (H’0002): Current output (+4~+20mA) Mode 3 (H’0003): Voltage output (0V~10V) Mode -1 (H’FFFF):

All channels are unavailable #3 X R/W CH2 output mode setting #4 X R/W CH3 output mode setting #5 X R/W CH4 output mode setting #6 X R/W The enabling function of table output Please refer to the table of CR#6 below for detail. Default = H’0000 #7 X R/W Enable table output function Bit 0~ bit 3 activate the table output function on CH1 ~ CH4. Modifying the parameters in output table during table output process is not allowed. 0: Stop, 1: Run, Default = H’0000. #8 X R/W Curves of table output function Please refer to the table of CR#8 for detail. Default = H’0000 #16 X R/W CH1 output signal value Voltage output range: K-32,000~K32,000 Current output range: K0~K32,000 Default:

K0 #17 X R/W CH2 output signal value #18 X R/W CH3 output signal value #19 X R/W CH4 output signal value #20 X R/W Present table output value of CH1 Default = K32767 #21 X R/W Present table output value of CH2 #22 X R/W Present table output value of CH3 #23 X R/W Present table output value of CH4