Model Numbering
TECHNICAL DATASHEET Chrome DC-UPS Module 24V 10A / DRU-24V10ACZ Highlights & Features Suitable for 24V system up to 10A Zero switch over time from loss of DC input to battery operation Built-in diagnostic monitoring for DC OK, Discharge and Battery Fail by relay contacts Full power over entire operating temperature range from -20°C to +60°C LED indicators for DC OK, Battery Charging, Battery Discharging, Battery Fail and Battery Reverse Polarity High MTBF > 500,000 hrs. as per Telcordia SR-332 Overvoltage / Overcurrent / Over temperature / Short circuit protections Safety Standards CB Certified for worldwide use Model Number: DRU-24V10ACZ Unit Weight:
0.14 kg (0.31 lb) Dimensions (L x W x D): 91.0 x 71.0 x 55.6 mm (3.58 x 2.80 x 2.19 inch) General Description Delta’s Chrome DC-UPS module is designed to use in small cabinets where space is very critical. The module requires less installation space due to its flat body with depth of only 55.6mm, 71mm wide and 91mm tall. The tough plastic case has flame retardant property certified to UL 94V-0 specification. The module supports 24Vdc system with external battery up to 12AH capacity and comes with potential free contacts for battery management signals and LED indicator for battery status.
The highly efficient convection cooled design is certified to major safety approvals including IEC/EN/UL 60950-1 for ITE and UL 508 for Industrial, which allows the module to be used reliably in most industrial applications. Model Information Chrome DC-UPS Module Model Numbering DR Z DIN Rail Z – Black Plastic Case, without Class I, Div 2 1 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev. 02) Model Number Input Voltage Range Rated Output Voltage Rated Output Current DRU-24V10ACZ 24-28Vdc 24Vdc typ. (Depends on Vin) 10.0A Max U – 24V 10A C DC-UPS Module Output Voltage Output Current Chrome Series
Battery Input / Output Characteristics
TECHNICAL DATASHEET Chrome DC-UPS Module 24V 10A / DRU-24V10ACZ Specifications Input Ratings / Characteristics Nominal Input Voltage 24Vdc Input Voltage Range 24-28Vdc Input Current Charging Mode 0.5A ± 0.1A Charging Time* Efficiency Charging Mode > 80.0% Buffering Mode > 99.0% *Charging time depends on the last state of discharged battery w.r.t. buffering time and load current. Output Ratings / Characteristics Battery Input / Output Characteristics 2 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev.
02) Output Voltage Range 23-28Vdc Output Current 10.0A Max Output Power 240W Max (24V, 10A) Voltage Drop Between Input and Output Charging Mode 0.2V between DC input to load Buffering Mode 0.3V between battery to load @ 10A load Nominal Battery Voltage 24Vdc, SLA Sealed lead acid battery 2 x 12Vdc, SLA Sealed lead acid battery Battery Voltage Range 23-28Vdc (continuously operating) 33Vdc Max (the maximum voltage that will not cause damage to the unit) 20Vdc Min (the voltage level of battery to enable “BAT Fail” function) Battery Capacity 3.3AH to 12AH Battery Fuse Auto 15A / 58V, MINI (Littelfuse) or similar in the battery path.
The battery fuse protects the wires between the battery and the unit. Battery Charging Mode CC-CV mode (constant current-constant voltage) at 0.5A End-of-Charge Voltage The unit always charges with fix input voltage value
Mechanical
TECHNICAL DATASHEET Chrome DC-UPS Module 24V 10A / DRU-24V10ACZ Buffering Time Mechanical Fig. 1 Buffering Time VS. Output Current 3 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev.
02) Output Buffering Time (min) Current 3.3AH 7.5AH 12AH 0.5A 400 900 1400 1A 180 398 654 2A 70 165 323 4A 28 72 160 6A 19 55 103 8A 11 22 49 10A 7 18 37 Case Cover / Chassis Plastic Dimensions (L x W x D) 91.0 x 71.0 x 55.6 mm (3.58 x 2.80 x 2.19 inch) Unit Weight 0.14 kg (0.31 lb) LED Indicator Green LED DC OK, Battery Charging (flash) Red LED Battery Fail Orange LED Reverse polarity, Battery Discharging (flash) Cooling System Convection Terminal Input / Output / Battery 6 Pins (Rated 300V/25A) Signal 6 Pins (Rated 300V/25A) Wire Input / Output / Battery AWG 24-12 Signal AWG 24-12 Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715 Noise (1 Meter from power supply) Sound Pressure Level (SPL)
Reliability Data
TECHNICAL DATASHEET Chrome DC-UPS Module 24V 10A / DRU-24V10ACZ Environment Protections *If the orange status LED is on, this indicates a failure in the installation. In this case, do not turn on power supply while the battery is connected. Danger of explosion! ** The unit will stop operating when the battery voltage detected is less than 22V ± 1V Reliability Data 4 All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (November 2018, Rev.
02) Surrounding Air Temperature Operating -20°C to +60°C (full power) Storage -25°C to +85°C Operating Humidity 5 to 95% RH (Non-Condensing) Operating Altitude 0 to 3,000 Meters Shock Test Operating IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 time per direction, 9 times in total Non-Operating IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11ms, 3 time per direction, 9 times in total Vibration Operating IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions Non-Operating IEC 60068-2-6, Random:
5Hz to 500Hz @ 2.09Grms); 20 min per axis for all X, Y, Z directions Pollution Degree 2 Overvoltage Buffering Mode 33Vdc Max will not cause damage to the unit, Latch Mode Overload / Overcurrent Buffering Mode Over Temperature Buffering Mode Short Circuit (at system) Buffering Mode Shutdown, Latch Mode Input Polarity Protection* Yes (DC OK = open contact, LED Status = Orange) Battery Polarity Protection* Yes (DC OK = open contact, LED Status = Orange) Wrong Battery Voltage Protection Shutdown, 35V Max (the maximum voltage that will not cause damage to the unit) Deep Discharge Protection Yes (22V ± 1V)** Degree of Protection IP20 Protection Against Shock Class III MTBF > 500,000 hrs.
as per Telcordia SR-332