User Manual EM303B General Purpose Inverter 1. In order to meet different needs of meters and external devices, the actual full scale voltage of M0/M1 is 10.9V, and the actual full scale current is 22mA. 2. Default of M0 and M1 is 0 ~ 10V. 3. If there is high demand for accuracy of analog output in application, please check idling output of M0 and M1 with multi-meter.

104 DC Bus Voltage DC Bus Voltage at 1.5 Times Rated Input Voltage Calculate the percentage= (DC bus voltage / the DC bus voltage at 1.5 times rated input voltage)*100%*A as the analog output 19 Output Power inverter rated power Calculate the percentage= (output power / rated power of inverter)*100%*A as the analog output 20 Feedback frequency /Output torque Fmax/Motor rated torque Feedback frequency output in speed mode, take the percentage of output frequency over the maximum frequency (Fmax) and then convert it to analogoutput. Torque output in torque mode, takes the percentage of output torque over motor rated torque and then converts it to analog output 21