User Manual EM303B General Purpose Inverter Upper limit/lower limit of analog output can be set to meet different meters and requirements. Final analog output signal= Output Lower Limit +Output gain*Analog output variables*(Output Upper Limit- Output Lower Limit) Analog output gain and output upper/lower limit (F2-22~F2-27) are corresponding to terminals M0 and M1, and irrelevant to the current running status. 8.4 F3 Group: Preset Speed Operation Parameters Through preset speed control terminals and 15 preset frequency commands,EM303B can provide 16 preset speeds by combining keypad numeric setting mode and analog setting mode.

Furthermore, it can be adjusted at any time through repeated addition analog input. Setting Preset Speed Terminals 105 No. Function Range Unit Default Type F2-22 M0 Output Lower Limit 0.00~100.00 % 0.00 ● F2-23 M0 Output Upper Limit 0.00~100.00 % 100.00 ● F2-24 M0 Output Gain 0.00~300.00 % 95.00 ● F2-25 M1 Output Lower Limit 0.00~100.00 % 0.00 ● F2-26 M1Output Upper Limit 0.00~100.00 % 100.00 ● F2-27 M1 Output Gain 0.00~300.00 % 95.00 ● No.

Function Range Unit Default Type F3-00 Preset Speed 1 0.00~Fmax/0.0~Fmax Hz 0.00 ● F3-01 Preset Speed 2 0.00~Fmax/0.0~Fmax Hz 5.00 ● F3-02 Preset Speed 3 0.00~Fmax/0.0~Fmax Hz 10.00 ● F3-03 Preset Speed 4 0.00~Fmax/0.0~Fmax Hz 15.00 ● F3-04 Preset Speed 5 0.00~Fmax/0.0~Fmax Hz 20.00 ● F3-05 Preset Speed 6 0.00~Fmax/0.0~Fmax Hz 25.00 ● F3-06 Preset Speed 7 0.00~Fmax/0.0~Fmax Hz 30.00 ● F3-07 Preset Speed 8 0.00~Fmax/0.0~Fmax Hz 35.00 ● F3-08 Preset Speed 9 0.00~Fmax/0.0~Fmax Hz 40.00 ● F3-09 Preset Speed 10 0.00~Fmax/0.0~Fmax Hz 45.00 ● F3-10 Preset Speed 11 0.00~Fmax/0.0~Fmax Hz 50.00 ● F3-11 Preset Speed 12 0.00~Fmax/0.0~Fmax Hz 50.00 ● F3-12 Preset Speed 13 0.00~Fmax/0.0~Fmax Hz 50.00 ● F3-13 Preset Speed 14 0.00~Fmax/0.0~Fmax Hz 50.00 ● F3-14 Preset Speed 15 0.00~Fmax/0.0~Fmax Hz 50.00 ● Terminal No.

Default Function X3 F2-02 3 Preset Speed Terminal 1 X4 F2-03 4 Preset Speed Terminal 2 X5 F2-04 5 Preset Speed Terminal 3 X6 F2-05 6 Preset Speed Terminal 4 X7 F2-06 10 Inverter Fault Reset