sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter 4.2.7 Fault Monitoring When fault occurs, inverter will enter fault monitoring status (The shared fault code can be viewed by FE-20~ FE-22.) See Table 4-3 for LED displays. Table 4-3 Fault Status Monitoring Data Select a code from E0-00~E0-31 to view its parameter on sub-menu of fault monitoring. For instance, see Figure 4-8 for viewing procedures. Referring to Figure 4-8, press or in fault monitoring status to view each fault status, and switch to E0 group fault code to view the last 3 faults status by pressing RES ESC . After fault is cleared, pressing STOP RESET will enable inverter to return initial power-on status from fault status.

47 Fault Code Display Fault 00 No fault SC Drive failure/Output Short circuit/EMC fault HOC Instantaneous overcurrent SOC Stable overcurrent HOU Instantaneous overvoltage SOU Stable overvoltage SlU Stable undervoltage/SOFT Soft-start failure IlP Input phase loss Ol OL inverter overload/OL1 motor overload (All displayed as OL) E0-00 OH Overheat OlP Output phase loss EXT External fault EST PID feedback loss/SPI communication fault/SCIfault INP Internal fault EEd Inverter EEPROM failure EEU Keypad EEPROM failure StP Autotuning cancelled SFE Autotuning coast-to-stop SrE Stator resistance error E0-00 SIE Idling current error E0-01 XXX Output Frequency at Fault E0-02 Output Current at Fault E0-03 DC Bus Voltage at Fault E0-04 Running Direction at Fault E0-05 Running Status at Fault E0-06 Stall Status at Fault E0-07 Working Time at Fault E0-08~E0-15 The same Function as E0-01~E0-07 The 1st Most Recent Fault E0-09~E0-23 The 2nd Most Recent Fault E0-24~E0-31 The 3rd Most Recent Fault