User Manual EM303B General Purpose Inverter 4.2.7 Fault Monitoring When fault occurs, inverter will enter fault monitoring status (The shared fault code can be viewed by FE-20~ FE-22.) See Table 4-3 for LED displays. Table 4-3 Fault Status Monitoring Data Select a code from E0-00~E0-31 to view its parameter on sub-menu of fault monitoring. For instance, see Figure 4-8 for viewing procedures. Referring to Figure 4-8, press or in fault monitoring status to view each fault status, and switch to E0 group fault code to view the last 3 faults status by pressing RES ESC . After fault is cleared, pressing STOP RESET will enable inverter to return initial power-on status from fault status.

47 Fault Code Display Fault 00 No fault SC Drive failure/Output Short circuit/EMC fault HOC Instantaneous overcurrent SOC Stable overcurrent HOU Instantaneous overvoltage SOU Stable overvoltage SlU Stable undervoltage/SOFT Soft-start failure IlP Input phase loss Ol OL inverter overload/OL1 motor overload (All displayed as OL) E0-00 OH Overheat OlP Output phase loss EXT External fault EST PID feedback loss/SPI communication fault/SCIfault INP Internal fault EEd Inverter EEPROM failure EEU Keypad EEPROM failure StP Autotuning cancelled SFE Autotuning coast-to-stop SrE Stator resistance error E0-00 SIE Idling current error E0-01 XXX Output Frequency at Fault E0-02 Output Current at Fault E0-03 DC Bus Voltage at Fault E0-04 Running Direction at Fault E0-05 Running Status at Fault E0-06 Stall Status at Fault E0-07 Working Time at Fault E0-08~E0-15 The same Function as E0-01~E0-07 The 1st Most Recent Fault E0-09~E0-23 The 2nd Most Recent Fault E0-24~E0-31 The 3rd Most Recent Fault