User Manual EM303B General Purpose Inverter and stop when FJOG and RJOG are on simultaneously. See 7.1 for detail of Jog operation.  Reverse jog is disabled when reverse is prohibited. Xi=13 UP: Terminal controls numeric frequency, and the stepping frequency rises. Xi=14 DOWN: Terminal controls numeric frequency, and the stepping frequency drops. During operation, if it is in stepping mode, the terminals are the hot keys for stepping frequency. Its speed rate can be set by F9-07.

Xi=15 Clearing the frequency enabled by UP/DOWN Xi=16 Acceleration/Deceleration prohibited When acceleration/deceleration prohibition terminal is on, acceleration/ deceleration command is prohibited, and the output frequency of inverter remains unchanged. When inverter is in overcurrent protection status, it runs as per the current limiting mode. Xi=17 Ramp to stop Xi=18 3-wire sequence stop control The function is NC stop button of 3-wire sequence. See F0-05 for details of terminal start/stop options.

Xi=19 Not used Xi=20 Switch drive control mode to V/F control mode No matter what drive control mode F0-02 is in, if the terminal is on, the drive control mode will be switched to V/F control mode, and its function is equivalent to F0-02=0. When the terminal is off, it returns the previous control mode automatically. Xi=21 Switch run command to terminal control When the terminal is on, no matter what run command mode F0-04 is in, and what status of the run command input 0 or input 1is, it is always in terminal control mode which is placed in the highest priority. The terminal control mode is set by F0-05.

Xi=22 Run command input 0 Xi=23 Run command input 1 The run command control modes can be selected through programming the run command inputs. See Table 7-1 for the correlation between run command control mode and run command input. Table 7-1 Correlation between run command control mode and run command inputs Programming mode of run command inputs is prior to F0-04 run command mode selection. Xi=24 Switch input control mode to speed control mode When the terminal is on, the present input control mode is switched to the speed control mode, and its function is equivalent to F0-03=0. After the terminal is off, inverter returns the previous input control mode automatically.

97 Run Command Input 0 Run Command Input 1 Run Command Control Mode OFF OFF F0-04 Start/Stop Mode OFF ON Keypad ON OFF RS485 ON ON External Terminal