User Manual EM303B General Purpose Inverter Xi=25 Switch input control mode to torque control mode When the terminal is on, the present control mode is switched to torque control mode. Its function is equivalent to F0-03=1. After the terminal is off, inverter returns the previous input control mode automatically. When the corresponding function terminals of Xi=24/25 are on simultaneously, terminal of Xi=24 is prior to terminal of Xi=25. If it is not set as SVC1, F0-02≠3 , it cannot be switched to torque control.
Xi=26 Not Used Xi=27 Switch speed input setting mode to primary speed setting mode In speed control mode, if the terminal is on, and then integrated speed input mode is switched to primary speed setting mode. After the terminal is off, inverter returns the previous input mode automatically. It is equivalent to setting F9-03 ones place=0 when it is on. Xi=28 Switch speed input setting mode to auxiliary speed setting mode In speed control mode, if the terminal is on, then the speed input setting mode is switched to auxiliary speed setting mode. Its function is equivalent to setting F9-03 ones place =1. After the terminal is off, inverter returns the previous setting mode automatically.
Xi=29 Switch primary speed setting mode to regular speed setting mode In speed control mode, if the terminal is on, then the primary speed setting mode is switched to regular speed setting mode. Its function is equivalent to setting F0-26=0. After the terminal is off, inverter returns the previous setting mode automatically. Xi=30 Switch regular speed input setting mode to numeric speed input setting mode In regular speed control mode, if the terminal is on, then the present regular speed setting mode of F0-06 is switched to the numeric speed input setting mode. Its function is equivalent to setting F0-06=0. After the terminal is off, inverter returns the previous setting mode automatically.
Xi=31 Switch jog input setting mode to jog numeric speed input setting mode In regular speed control mode, if the terminal is on, then the present jog speed setting mode is switched to jog numeric speed input setting mode. Its function is equivalent to setting the tens place of F9-03=0. After the terminal is off, inverter returns the previous setting mode automatically. Xi=32 ~ 34 Not used Xi=35 Switch regular torque input setting to numeric torque input setting In regular speed control mode, if the terminal is on, then the present regular torque setting mode is switched to the numeric torque input. Its function is equivalent to setting F5-11=0.
After the terminal is off, inverter returns the previous setting mode automatically. Xi=36 Not used Xi=37 PID positive/negative function switch In the process of process PID control operation, if the input signal of the function 98