Step 5 Hardware SW setting K6PM-THS sensor has DIP switch to set the following contents. K6PM-TH Main Unit does not have hardware SW. As the device configuration in this guide, the number of K6PM-THS sensor to connect is one unit. Set SW6 to "ON: With terminating resistance". Also, set SW7 to "ON: With detection" for use of function which detect the sensor angle deviation. The sensor number is "00001" in the default state. In this guide, the setting is explained by default. ● ● RS-485 terminating resistance: Set it to the sensor which is the most far from Main Unit.

Sensor Sensor Sensor Main Unit Terminating resistance ON Main Unit Terminating resistance OFF Terminating resistance ON ● ● Detection of sensor angle deviation: The function which detect the angle deviation after installing the sensor. ○ Angle deviatio Ч Moving in horizontal Ч Rotation of gravity axis direction Sensor Sensor Sensor Sensor Gravity direction 9 SW Setting contents Value 1 to 5 K6PM-TH sensor number setting Set in binary with ON as 1 and OFF as 0 (Pin 1: Least significant bit, Pin 5: Most significant bit) 00001 to 11111: K6PM-TH sensor number 1 to 31 00000: Not used. Factory default: 00001 6 RS-485 terminating resistance OFF: Without terminating resistance (factory default) ON:

With terminating resistance 7 The detection of the K6PM-TH sensor angle deviation OFF: No detection (factory default) ON: With detection 8 Reserved. ----