ѓ ENGLISH ѓ Thank you for choosing Delta’s DVP series PLC. DVP06XA-E2 mixed analog input/output module receives external 4 points of analog input signals (voltage or current) and converts them into 16-bit digital signals. For the analog signal output, DVP06XA-E2 receives 2 groups of 16-bit digital data coming from the PLC MPU and converts the digital data into 2 points of analog output signals (voltage or current). In addition, you can access the data in the module by applying FROM/TO instructions or read the average value or write the output value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).
EN a DVP06XA-E2 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP06XA-E2, or to prevent an accident from damaging DVP06XA-E2, the control cabinet in which DVP06XA-E2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP06XA-E2 is installed can be unlocked with a special tool or key. EN a DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP06XA-E2 is powered up. After DVP06XA-E2 is disconnected, Do NOT touch any terminals in a minute.
Make sure that the ground terminal on DVP06XA-E2 is correctly grounded in order to prevent electromagnetic interference. FR a DVP06XA-E2 est un module OUVERT. Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR a Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP06XA-E2 pourra ktre endommagй.
Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP06XA-E2. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. ѓ Product Profile & Dimension Model Name Direct mounting hole Terminal No. I/O module connection port Terminal No. ѓ External Wiring *1: When performing analog input, please isolate other power wirings. *2: When the XA module is connected to current signals, make sure you short-circuit "V+” and “I+” terminals. *3:
If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor. *4: When performing analog output, please isolate other power wirings. *5: If the ripples at the loaded output terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor. *6: Please connect the terminal on both the power module and XA module to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet.
- 1 - me ing Power / A D / Error indicators Removable I/O terminal I/O module clip Mounting sl (35mm) 90 98 106 110 I/O module connection po 62 61.5 (Unit: mm) 70 78 [ Figure 1 ] No. port No. 06XA -E2 4A I/ 2AO 90 98 106 110 [ Figure 1 ]
y Input: Active-type y Input: Passive-type y Output AC motor drive, recorder, scale valve... CH5 *5 CH5 Voltage output VO1 IO1 AG Current output Shielded cable*4 CH6 VO2 IO2 AG CH6 AC motor drive, recorder, scale valve...
Shielded cable*4 Terminal of power module 0V 24V DC24V DC/DC +15V -15V AG [ Figure 4 ] ѓ I/O Terminal Layout Class 3 grounding (100 or less) converter 1 2 3 4 5 6 7 8 9 10 11 12 AG 1 2 3 4 5 6 7 8 9 10 11 12 - 2 - AG Voltage input CH1 1M UIN + *3 V VI11 I+ 1+ 250 1M - - Shielded cable*1 FE AG Current input CH4 1M UIN + *2 V VI44 I+ 4+ 250 1M - - Shielded cable*1 FE Terminal of ower module 0V DC/DC +15V 24V Converter AG -15V Grounding (100 or less) CH1 CH4 [ Figure 2 ] AG Voltage input + CH1 1M UIN V VI11 1+ 250 - *3 I+ - 1M FE Shielded cable*1 AG Cu -rrent input C *2H4 V I44 ++ 1 1M 250 M VI4- + FE Shielded cable*1 Terminal of power module 0V DC/DC +15V 24V Converter AG -15V Grounding (100 or less) CH1 CH4 [ Figure 3 ] V1+ I1+ VI1- V2+ I2+ VI2- V3+ I3+ VI3- V4+ I4+ V DVP06XA-E2 (4AI/2AO) 24V 0V FE FE FE VO1 IO1 AG VO2 IO2 A I1+ VI1- V2+ I2+ VI2- V3+ I3+ VI3- V4+ I4+ V
ѓ Electrical Specifications ѓ Functions Specifications - 3 - DVP06XA-E2 Power supply voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) Max. rated power 2.5W, supplied by external power source consumption Connector European standard removable terminal block (Pin pitch: 5mm) Operation: 0°C~55°C (temp.), 5~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity) Operation/storage Vibration/shock International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) immunity The modules are numbered from 0 to 7 automatically by their distance from MPU. Max. 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Series connection to DVP-PLC MPU Common specifications Digital data format 2’s complement of 16 bits Response time 400μs / each channel ±0.5% when in full scale within the range of (25°C, 77°F); ±1% when in full scale within the range of (0 ~ 55°C, 32 ~ 131°F) Overall accuracy Optical coupler isolation between digital circuits and analog circuits. No isolation among analog channels. 500VDC between digital circuits and Ground. 500VDC between analog circuits and Ground. 500VDC between analog circuits and digital circuits.
500VDC between 24VDC and Ground Isolation Analog / Digital Voltage input Current input Analog input channel 4 channels / each module Range of analog input ±10V ±5V ±20mA 0 ~ 20mA 4 ~ 20mA Range of digital ±32,000 ±32,000 ±32,000 0 ~ 32,000 0 ~ 32,000 conversion Max./Min. output range ±32,384 ±32,384 ±32,384 -384 ~+32,384 -384 ~+32,384 of digital data Hardware Resolution 14 bits 14 bits 14 bits 13 bits 13 bits Input impedance ≧1MΩ 250Ω Range of absolute input ±15V ±32mA Supported. Available for setting up sampling range in CR#8 ~ CR#11. Range: K1 ~ K100.
Average Function Self-diagnosis Upper and lower bound detection in all channels Digital / Analog Voltage output Current output Analog output channel 2 channels / each module Range of analog output -10V ~ 10V 0 ~ 20mA 4mA ~ 20mA Range of digital -32,000 ~ +32,000 0 ~ +32,000 0 ~ +32,000 conversion Max./Min. input range of -32,768 ~ +32,767 0 ~ +32,767 -6,400 ~ +32,767 digital data Hardware Resolution 14 bits 14 bits 14 bits Max. output current 5mA - Tolerance load 1KΩ ~ 2MΩ 0 ~ 500Ω impedance
ѓ Control Register - 4 - Output impedance 0.5Ω or lower Voltage output is protected by short circuit. Short circuit lasting for too long may cause damage on internal circuits. Current output can be open circuit. Protection CR# Attrib. Register name Explanation #0 O R Model name Set up by the system: DVP06XA-E2 model code = H’00C4 #1 O R Firmware version Display the current firmware version in hex. #2 O R/W CH1 Input mode setting Input mode: Default = H’0000. Take CH1 for example:
Mode 0 (H’0000):Voltage input (±10V) Mode 1 (H’0001):Voltage input (±5V) Mode 2 (H’0002):Voltage input (0 ~+10V) Mode 3 (H’0003):Voltage input (0 ~+5V) Mode 4 (H’0004):Current input (±20mA) Mode 5 (H’0005):Current input (0 ~+20mA) Mode 6 (H’0006):Current input (4 ~+20mA) Mode -1 (H’FFFF):Channel 1 unavailable #3 O R/W CH2 Input mode setting #4 O R/W CH3 Input mode setting #5 O R/W CH4 Input mode setting #6 O R/W CH5 output mode setting Output mode: Default = H’0000. Take CH5 for example:
Mode 0 (H’0000):Voltage output (±10V) Mode 1 (H’0001):Current output (0~+20mA) Mode 2 (H’0002):Current output (4~+20mA) Mode -1 (H’FFFF):Channel 5 unavailable #7 O R/W CH6 output mode setting #8 O R/W CH1 sampling range Set sampling range in CH1 ~ CH4: Range = K1 ~ K100 Default = K10 #9 O R/W CH2 sampling range #10 O R/W CH3 sampling range #11 O R/W CH4 sampling range #12 X R CH1 average input value Average value of input signals at CH1 ~ CH4 #13 X R CH2 average input value #14 X R CH3 average input value #15 X R CH4 average input value #16 X R/W CH5 output signal value Voltage output range: K-32,000~K32,000. Current output range: K0~K32,000. Default: K0.
#17 X R/W CH6 output signal value #20 X R CH1 present input value Present value of input signals at CH1 ~ CH4 #21 X R CH2 present input value #22 X R CH3 present input value #23 X R CH4 present input value #28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of CH1 ~ CH6 Default = K0. Definition of Offset in DVP06XA -E2:
The corresponding voltage (current) input value when the digital output value = 0 #29 O R/W Adjusted Offset value of CH2 #30 O R/W Adjusted Offset value of CH3 #31 O R/W Adjusted Offset value of CH4 #32 O R/W Adjusted Offset value of CH5 #33 O R/W Adjusted Offset value of CH6 #34 O R/W Adjusted Gain value of CH1 Set the adjusted Gain value in CH1 ~ CH6 Default = K16,000. Definition of Gain in DVP06XA-E2: The corresponding voltage (current) input value when the digital output value = 16,000. #35 O R/W Adjusted Gain value of CH2 #36 O R/W Adjusted Gain value of CH3 #37 O R/W Adjusted Gain value of CH4 #38 O R/W Adjusted Gain value of CH5 #39 O R/W Adjusted Gain value of CH6