2014-04-30 5012614903-03SD
ENGLISH Thank you for choosing Delta DVP-SE. DVP-SE is a 12-point (8DI + 4DO) PLC MPU, offering various instructions and with 16k steps program memory, able to connect to all DVP Slim type series extension modules and high-speed extension modules, including digital I/O (max. 480 I/O points) and analog modules (for A/D, D/A conversion and temperature measurement). 2 points of 100 kHz and 2 points of 10 kHz high-speed pulse output satisfy all kinds of applications. DVP-SE is small in size, and can be installed easily. Users do not have to install any batteries in DVP-SE series PLCs. The PLC programs and the latched data are stored in the high-speed flash memories.
EN DVP-SE is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP-SE, or to prevent an accident from damaging DVP-SE, the control cabinet in which DVP-SE is installed should be equipped with a safeguard. For example, the control cabinet in which DVP-SE is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP-SE is powered up. After DVP-SE is disconnected, Do NOT touch any terminals in a minute.
Make sure that the ground terminal on DVP-SE is correctly grounded in order to prevent electromagnetic interference. FR DVP-SE est un module OUVERT. Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVP-SE pourra ktre endommagй.
Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVP-SE. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. Product Profiles 16 37.4 8 8 1 60 2 3 4 ss 5 9 13 14 3 6 90 10 11 15 12 D V P -12S E - 7 12 [Figure 1] 3 Unit: mm 1. POWER, RUN, ERROR, COM1 indicator 9. Nameplate 2. RUN/STOP switch 10. Right-side extension port 3. COM1 port (Mini USB) 11. DIN rail mounting slot (35mm) 4. I/O terminals and COM3 comm. port (RS-485) 12. Extension unit clip 5. I/O point and COM2, COM3 indicator 13.
COM2 communication port (RS-485) 6. Ethernet communication port 14. Mounting rail for extension module 7. DIN rail clip 15. DC power input 8. Mounting hole for extension module 16. Left-side module connection port Electrical Specifications - 1 - Model DVP12SE11R DVP12SE11T Item 24 VDC (-15 to 20%) voltage (with counter-connection protection on the polarity of DC input power) DVPPS01/PS02: input 100 to 240 VAC, output 24 VDC/1A (PS02: 2A) Power supply Connector European standard removable terminal block (Pin pitch: 3.5mm) Operation Maximum power loss time is 10ms or less. Inrush curren t Max.
7.5 A@24 VDC, I2t = 0.25 A2S Fuse capacity 2.5 A/30 VDC, Polyswitch Power consu mption 1.8 W 1.5 W Power protec tion With counter-connection protection on the polarity of DC input power Insulation res istance > 5 MΩ (all I/O point-to-ground: 500 VDC)
#1: UP, ZP must work with external auxiliary power supply 24 VDC (-15 to +20%), rated consumption approx. 1mA/point. #2: Life curves Operation(X10 ) 3 3,000 1,000 2,000 120 VAC, resistive 200 300 500 100 [ Figure 2 ] #3: Load = 0.5A I/O Configuration 50 current(A) 0.5 0.1 0.2 0.3 0.7 1 2 - 2 - Model DVP12SE11R DVP12SE11T Item ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog & Communication I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3):
26MHz ~ 1GHz, 10V/m Noise immunity The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole). Grounding Operation: 0 to 55°C (temp.), 50 to 95% (humidity), Pollution degree 2 Storage: -25 to 70°C (temp.), 5 to 95% (humidity) Operation / storage Vibration / shock International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) resistance Weight (g) 145 135 Spec. Input Points Items 24 VDC (-15 to 20%) single common port input Input No. X0 to X2 X3 to X7 Input type DC (SINK or SOURCE) Input current (±10%) 24 VDC, 5 mA Input impedance 4.7 kΩ Max.
frequency 100 kHz 10 kHz Action Off On > 15 VDC level On Off Response Off On time On Off Filter time Adjustable within 0 ~ 20ms by D1020 (Default: 10ms) Spec. Output Points Items Relay Transistor Output No. Y0 to Y3 Y0, Y2 Y1, Y3 Max. frequency 1 Hz 100 kHz 10 kHz Working voltage 250 VAC, 5 to 30 VDC #1 Resistive 1.5 A/1 point (5 A/COM) 0.5 A/1 point (2 A/COM) Max. load Inductive #2 15 W (30 VDC) Lamp 20 WDC/100 WAC 2.5 W (30 VDC) Response Off On Approx.
10 ms 2 μs #3 20 μs #3 time On Off 3 μs #3 30 μs #3 30 V 24 DC, indu 0 VAC, i ctive nduc 120 VA C, in ductive (cosψ=0.4 30 in VDC, ductive (t =40ms) Input Output I/O Configuration Model Point Type Point Type Relay Transistor DVP12SE11R 8 DC (Sink Or Source) 4 Relay S/ S S/ S X0 X0 X1 X1 X2 X2 X3 X3 X4 X4 X5 X5 X6 X6 X7 X7 DVP12SE11T Transistor C0 Y0 Y0 Y1 Y1 Y2 Y2 Y3 Y3 UP ZP SG SG COM3+ COM3+ COM3- COM3-
Dimension & Installation Please install the PLC in an enclosure with sufficient space around it to allow heat dissipation, See [Figure 3]. Direct Mounting: Use M4 screw according to the dimension of the product. DIN Rail Mounting: When mounting the PLC to 35mm DIN rail, be sure to use the retaining clip to stop any side-to-side movement of the PLC and reduce the chance of wires being loose. The retaining clip is at the bottom of the PLC. To secure the PLC to DIN rail, pull down the clip, place it onto the rail and gently push it up. To remove the PLC, pull the retaining clip down with a flat screwdriver and gently remove the PLC from DIN rail. Wiring 1.
Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. See the figure in the right hand side for its specification. PLC terminal screws should be tightened to 1.90 kg-cm (1.65 in-lbs) and please use only 60/75єC copper conductor. 22-16AWG 2. DO NOT wire empty terminal. DO NOT place the I/O signal cable in the same wiring circuit. 3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. Tear off the sticker on the heat dissipation hole for preventing alien substances from dropping in to ensure normal heat dissipation of the PLC. Power Supply The power input of DVP-SE is DC. When operating DVP-SE please note the following points: 1.
The power is connected to two terminals, 24 VDC and 0 V, and the range of power is 20.4 to 28.8 VDC. If the power voltage is less than 17.5 VDC, the PLC will stop running, all outputs will go “Off”, and the ERROR indicator will start to blink continuously. 2. The power shutdown for less than 10ms will not affect the operation of the PLC. However, the shutdown time that is too long or the drop of power voltage will stop the operation of the PLC, and all outputs will go off. When the power returns to normal status, the PLC will automatically resume the operation. (Please take care of the latched auxiliary relays and registers inside the PLC when doing the programming).
Safety Wiring Since DVP-SE is only compatible with DC power supply, Delta’s power supply modules (DVPPS01/DVPPS02) are the suitable power supplies for DVP-SE. We suggest you install the protection circuit at the power supply terminal to protect DVPPS01 or DVPPS02. See the figure below. - 3 -