Delta Electronics MS300 — 6-1 Control Terminal Specifications

Chapter 6 Control Terminals  MS300 6-1 Control Terminal Specifications Control Terminal Distribution Diagram Control Terminal Location Diagram Figure 6-6 Figure 6-7 Wiring precautions: 1. The factory default is +24 V/S1/S2 short-circuited by jumper, as shown in Area 1 in Figure 6-6. Refer to Figure 4-2 in Chapter 4 WIRING for details. 2. Use the +24V power supply of the safety function (as shown in Area 2 in Figure 6-7) for STO only. Do NOT use it for other purposes. 3. The RELAY terminal uses the PCB terminal block (as shown in Area 3 in Figure 6-6):  Tighten the wiring with a 3.5 mm width and 0.6 mm thickness slotted screwdriver.

 The ideal length of stripped wire at the connection side is 6–7 mm.  When wiring bare wires, ensure that they are perfectly arranged to go through the wiring holes. 4. The Control terminal uses the push-in spring terminal block (as shown in Area 4 in Figure 6-6):  Tighten the wiring with a 2.5 mm width and 0.4 mm thickness slotted screwdriver.  The ideal length of stripped wire at the connection side is 9 mm.  When wiring bare wires, ensure that they are perfectly arranged to go through the wiring holes.

Wiring Specifications of Control Terminal Table 6-1 6-4 Terminal Name Wiring Specifications of Control Terminals Stripping Maxim Length (mm) Wire G um Minimum auge Wire Gauge T Tightening orque (±10%) RELAY Terminals Solid 1.5 m 6–7 [16 A m2 0.2 mm2 WG] [24 AWG] 5 Kg-cm [4.3 lb-in.] [0.49 Nm] Strand Control Terminals S Solid 0.75 9 [18 A mm2 WG] 0.25 mm2 [24 AWG] m2 WG] Strand tranded with ferrules with plastic sleeve 0.5 m 9 [20 A