Delta · 4 стр.
PG02 instruction en (EN)
Оригинальное название: PG02 instruction en
Похожие инструкции
Текст документа
2007-07-12 5011606104-PGE4 PG-02 Pulse Generator Card for VFD-B Series Installation Instruction Installation 1 to 2HP (0.75kW to 1.5kW) 3 to 5HP (2.2kW to 3.7kW) Insulation spacer Insulation spacer PG-02 PG-02 PG Card Terminal Plastic Stand off Control board PG Card Terminal Control board 7.5HP (5.5kW) and above Control Terminals Block Designations Insulation spacer Connect to VFD-B series control board Wiring Terminals A/O B/O COM VP DCM A PG-02 PG-02 FSW2 FSW1 OC 12V Plastic Stand off PG Card Terminal Select the power source and output of Pulse Generator A 5V TP B B
2 PG Card and Pulse Generator A. Basic Wiring Diagram B. Basic Wiring Diagram with RPM Meter Attached. None Fused Breaker R/L1 NFB R/L1 T/L3 S/L2 S/L2 T/L3 PG PG-02 and Pulse Generator Connections Pulse Generator Output 12V DC PG-02 and Pulse Generator Connections C. When Pulse Generators is Open Collector type, please wire as following.
R/L1 NFB S/L2 T/L3 Output 12V DC PG-02 and Pulse Generator Connections R/L1 U/T1 S/L2 V/T2 T/L3 W/T3 VFD-B OC12V TP5V Motor IM 3~ A A A A B B B B VP +5V DCM GND E A/O B/O COM RPM m OC12V TP5V A A B B VP DCM E A/O B/O COM A B B +5V GND RPM m E NFB R/L1 U/T1 S/L2 V/T2 T/L3 W/T3 PG-02 OC12V Factory Default TP 5V Motor IM 3~ A A A A PG B B B B +12V VP DCM GND E PG-02 OC12V Factory Default TP 5V A A B B VP DCM E GND R/L1 U/T1 S/L2 V/T2 T/L3 W/T3 PG-02 OC12V Factory Default TP 5V Motor IM 3~ A A A PG B B B +12V VP DCM GND E A A B B VP DCM E
3 PG-02 Terminal Descriptions Terminals Wiring Notes The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit / trunking. 1. Please use a shield cable to prevent interference. Do not run control wire parallel to any high voltage AC power line (220 V and up). 2. Connect shielded wire to E only. 3. Recommended wire size 0.21 to 0.81mm 2 (AWG24 to AWG18). 4. Wire length: Terminal Symbols Descriptions VP Power source of PG-02 (FSW1 can be switched to 12V or 5V) Output Voltage: (+12VDC ±5% 200mA) or (+5VDC ±2% 400mA) DCM Power source (VP) and input signal (A, B) common Input signal from Pulse Generator. Input type is selected by FSW2.
Maximum 500KP/Sec A/O, B/O PG-02 output signal for use with RPM Meter. Maximum DC24V 300mA COM PG-02 output signal (A/O, B/O) common. Types of Pulse Generators Maximum Wire Length Wire Gauge Output Voltage 50m 1.25mm2 (AWG16) or above Open Collector 50m Line Driver 300m Complementary 70m
4 Types of Pulse Generators ASIA DELTA ELECTRONICS, INC. TAOYUAN Plant/ 31-1, SHIEN PAN ROAD, KUEI SAN INDUSTRIAL ZONE TAOYUAN 333 TEL: 886-3-362-6301 FAX: 886-3-362-7267 NORTH/SOUTH AMERICA DELTA PRODUCTS CORPORATION Sales Office/ P.O. BOX 12173 5101 DAVIS DRIVE RTP, NC 27709 U. S. A. TEL: 1-919-767-3813 FAX: 1-919-767-3969 EUROPE DELTRONICS (Netherlands) B.V. Sales Office/ Industriegebied Venlo Nr. 9031 Columbusweg 20 NL-5928 LC Venlo The Netherlands TEL: 31-77-324-1930 FAX:
31-77-324-1931 Types of Pulse Generators FSW1 and FSW2 switches 5V 12V Output Voltage VCC O/P 0V FSW2 FSW1 OC12V TP 5V FSW2 FSW1 OC12V TP 5V Open collector VCC O/P 0V FSW2 FSW1 OC12V TP 5V FSW2 FSW1 OC12V TP 5V Line driver Q Q FSW2 FSW1 OC12V TP 5V FSW2 FSW1 OC12V TP 5V Complimentary VCC O/P 0V FSW2 FSW1 OC12V TP 5V FSW2 FSW1 OC12V TP 5V