omron — 6 Parameter Table

6 Parameter Table ENGLISH 6 Parameter Table This parameter table shows the most impor- tant parameters. Default settings are bold type. Refer to the instruction manual for a complete list of parameters. I80E-EN J1000 Quick Start Guide 21 Par. Name Description b2-03 DC Inj. Braking Time/DC Excitation Time at Start Sets the time of DC Injection Brak- ing at start in units of 0.01 seconds. Disabled when set to 0.00 seconds. b2-04 DC Inj. Braking Time at Stop Sets the DC Injection Braking time at stop. Disabled when set to 0.00 seconds. Acceleration/ Deceleration C1-01 Accel Time 1 Sets the acceleration time 1 from 0 to the max. output frequency.

C1-02 Decel Time 1 Sets the deceleration time 2 from the max. output frequency to 0. C2-01 S-Curve 1 S-curve at acceleration start. C2-02 S-Curve 2 S-curve at acceleration end. C2-03 S-Curve 3 S-curve at deceleration start. C2-04 S-Curve 4 S-curve at deceleration end. Slip Compensation C3-01 Slip Com- pensation Gain • Increase if the speed is lower than the frequency reference • Decrease if the speed is higher than the frequency reference. C3-02 Slip Com- pensation Delay Time • Decrease the setting when the slip compensation is too slow. • Increase the setting when the speed is not stable.

Torque Compensation C4-01 Torque Compensa- tion Gain • Increase this setting when the torque response is slow • Decrease this setting when speed/ torque oscillations occur. Duty Mode and Carrier Frequency C6-01 Normal/ Heavy Duty Selection 0: Heavy Duty (HD) Constant torque applications 1:Normal Duty (ND) Variable torque application Par. Name Description Initialization Parameters A1-01 Access Level Selection Selects which parameters are accessible via the digital operator. 0:Operation only 2:Advanced Access Level A1-03 Initialize Parameters Resets all parameters to default. (returns to 0 after initialization) No Initialize 2220: 2-Wire Initialization 3330:

3-Wire Initialization Operation Mode Selection b1-01 Frequency Reference Selection 0:Operator - d1-†† values 1:Analog input A1 2:Serial Comm.option 3:Potentiometer Option b1-02 Run Command Selection 0:Operator - RUN and STOP keys 1:Terminals - Digital Inputs 2:Serial Comm.option b1-03 Stopping Method Selection Selects the stopping method when the run command is removed. 0:Ramp to Stop 1:Coast to Stop b1-04 Reverse Operation Selection 0:Reverse enabled 1:Reverse prohibited b1-14 Phase Order Selection Switches the output phase order.

0:Standard 1:Switch phase order DC Injection Braking b2-02 DC Injection Braking Current Sets the DC Injection Braking cur- rent as a percentage of the drive rated current.