omron — 6 Parameter Table

6 Parameter Table 22 I80E-EN J1000 Quick Start Guide Par. Name Description C6-02 Carrier Fre- quency Selection 1:2.0 kHz 2:5.0 kHz 3:8.0 kHz 4:10.0 kHz 5:12.5 kHz 6:15.0 kHz 7:Swing PWM F: User defined Frequency References d1-01 to d1-08 Frequency Reference 1 to 8 Set the multi-speed references 1 to 8 d1-17 Jog Speed Jog speed V/f Pattern E1-01 Input Voltage Set- ting Input Voltage E1-04 Max. Out- put Freq. For a linear V/f characteristics, set the same values for E1-07 and E1- 09. In this case, the setting for E1- 08 will be disregarded. Ensure that the four frequencies are set according to these rules or OPE10 fault will occur:

E1-04 ≥ E1-06 ≥ E1-07 ≥ E1-09 Output voltage (E1-05) (E1-08) (E1-10) (E1-09) (E1-07) (E1-06) (E1-04) Output frequency E1-05 Max. Out- put Voltage E1-06 Base Fre- quency E1-07 Middle Out- put Freq. E1-08 Mid. Out- put Voltage E1-09 Min. Out- put Freq. E1-10 Min. Out- put Voltage Motor Data E2-01 Motor Rated Current Motor rated current in Ampere. E2-02 Motor Rated Slip Motor rated slip in hertz (Hz). Par. Name Description E2-03 Motor No-Load Current Magnetizing current in Ampere. E2-05 Motor Line- to-Line Resistance Sets the phase-to-phase motor resistance in ohms. Digital Input Settings H1-01 to H1-05 DI S1 to S5 Function Selection Selects the function of terminals S1 to S5.

A list of the major functions can be found at the table end. Digital Output Settings H2-01 DO MA/MB Function Set the function for the relay output MA-MB-MC. Major functions are listed at the end of the table. Analog Input Setting H3-01 A1 Signal Level Sel. 0:0 to +10 V (neg. input is zeroed) 1:0 to +10 V (bipolar input) 2:4~20mA (9 bit input) 3:0~20mA H3-03 A1 Gain Sets the input value in % at 10 V/ 20 mA analog input. H3-04 A1 Bias Sets the input value in % at 0 V/0 mA/4 mA analog input. Analog Input Setting H4-01 AM Monitor Selection Enter value equal to U1-†† monitor values. Example: Enter “103” for U1-03. H4-02 AM Gain Sets terminal AM output voltage equal to 100% monitor value.

H4-03 AM Bias Sets terminal AM output voltage equal to 0% monitor value. Motor Overheat Protection L1-01 Motor Overload Prot. Sel. Sets the motor overload protection. 0:Disabled 1:Standard fan cooled motor 2:Standard blower cooled motor L1-02 Motor Overload Prot. Time Sets the motor overload protection time in min. Normally no change is necessary.