4-2 Function Mode 4 Functions *1. When either the control circuit terminal block or the coil is turned ON, these settings are ON. The control circuit terminal block has the priority for the multi-function input terminals. If the master cannot reset the coil ON status because of communication disconnection, turn the control circuit terminal block from ON to OFF in order to turn off the coil. *2. The content of a communications error is retained until a fault reset is input. (Can be reset during operation.) Holding Register Number List *1. The Inverter's rated current is "1000". *2. The second decimal place is ignored when the value is over 10000 (100.0 seconds). 4-77 Coil No.
Function name R/W Description 0017h Frequency arrival signal (Over set frequency) R 1: ON 0: OFF 0018h Frequency arrival signal (At a constant speed) R 1: ON 0: OFF 0019h Signal during RUN R 1: ON 0: OFF 001Ah Data writing R 1: Writing 0: Normal 001Bh CRC error R 1: Error 0: No error *2 001Ch Overrun error R 1: Error 0: No error *2 001Dh Framing error R 1: Error 0: No error *2 001Eh Parity error R 1: Error 0: No error *2 001Fh Check sum error R 1: Error 0: No error *2 Register No. Function name Parameter No. R/W function Data Resolution 0001h Frequency reference R/W 0 to 4000 (Enable when A001 = 03) 0.1 [Hz] 0002h Inverter status R 0: Initial status 1: Not used. 2: Stop 3: RUN 4:
Free-run stop 5: Jogging 6: DC injection braking 7: Retry 8: Trip 9: Undervoltage 0003h to 009h Not used 000Ah Output frequency monitor d001 R 0 to 4000 0.1 [Hz] 000Bh Output current monitor d002 R 0 to 2000 *1 0.1 [%] 000Ch Rotation direction monitor d003 R 0: Stop 1: Forward 2: Reverse