4-2 Function Mode 4 Functions *1. The Inverter's rated current is "1000". *2. The second decimal place is ignored when the value is over 10000 (100.0 seconds). 4-80 Register No. Function name Parameter No. R/W function Data Resolution 0041h Multi-step speed reference 6 A026 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0042h Multi-step speed reference 7 A027 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0043h Multi-step speed reference 8 A028 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0044h Multi-step speed reference 9 A029 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0045h Multi-step speed reference 10 A030 R/W 0/Starting frequency to Max.
frequency 0.1 [Hz] 0046h Multi-step speed reference 11 A031 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0047h Multi-step speed reference 12 A032 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0048h Multi-step speed reference 13 A033 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 0049h Multi-step speed reference 14 A034 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 004Ah Multi-step speed reference 15 A035 R/W 0/Starting frequency to Max. frequency 0.1 [Hz] 004Bh Jogging frequency A038 R/W 0/Starting frequency to 999 0.01 [Hz] 004Ch Jogging stop selection A039 R/W 0: Free-run stop 1: Deceleration stop 2:
DC injection braking stop 004Fh Manual torque boost voltage A042 R/W 0 to 200 0.1 [%] 0050h 2nd manual torque boost voltage A242 R/W 0 to 200 0.1 [%] 0051h Manual torque boost frequency A043 R/W 0 to 500 0.1 [%] 0052h 2nd manual torque boost frequency A243 R/W 0 to 500 0.1 [%] 0053h V/f characteristics selection A044 R/W 00: Constant torque characteristics (VC) 01: Special reduced torque characteristics (Special VP) 02: Intelligent sensor-less vector control (iSLV) 0054h 2nd V/f characteristics selection A244 R/W 0055h Output voltage gain A045 R/W 20 to 100 1. [%] 0056h Automatic torque boost voltage compensation gain A046 R/W 0 to 255 1.
[%] 0057h 2nd automatic torque boost voltage compensation gain A246 R/W 0 to 255 1. [%] 0058h Automatic torque boost slip compensation gain A047 R/W 0 to 255 1. [%]