4-2 Function Mode „ Specifications of Multi-function Output Terminals P1 to P5 •Below are the specifications of multi-function output terminals P1 to P5. Electrical characteristics Between each terminal and PC Voltage drop 4 V max. at power-on Max. allowable voltage: 27 V DC Max. allowable current: 50 mA 4 Functions „ Specifications of the Relay Output Terminals •The relay output terminals have an SPDT contact configuration. Below is its operation. Inside the Inverter (Default value:
C036 = 01) (Example) When the relay output terminals are used for alarm 4-93 P5 PC P1 Inside the Inverter P5 PC P1 C031 to C035 set values Power supply Output status 00 (NO contact) ON ON OFF OFF 01 (NC contact) ON ON OFF OFF MC MA MB C036 set values Power Inverter status Output terminal status MA-MC MB-MC 00 ON Abnormal Closed Open Normal Open Closed OFF Open Closed 01 (Default) ON Abnormal Open Closed Normal Closed Open OFF Open Closed Resistance load Inductive load MA-MC Max. contact capacity 250 V AC, 2 A 30 V DC, 8 A 250 V AC, 0.2 A 30 V DC, 0.6 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA MB-MC Max.