omron — Multi-function Output Terminal Contact Selection

4-2 Function Mode „ Specifications of Multi-function Output Terminals P1 to P5 •Below are the specifications of multi-function output terminals P1 to P5. Electrical characteristics Between each terminal and PC Voltage drop 4 V max. at power-on Max. allowable voltage: 27 V DC Max. allowable current: 50 mA 4 Functions „ Specifications of the Relay Output Terminals •The relay output terminals have an SPDT contact configuration. Below is its operation. Inside the Inverter (Default value:

C036 = 01) (Example) When the relay output terminals are used for alarm 4-93 P5 PC P1 Inside the Inverter P5 PC P1 C031 to C035 set values Power supply Output status 00 (NO contact) ON ON OFF OFF  01 (NC contact) ON ON OFF OFF  MC MA MB C036 set values Power Inverter status Output terminal status MA-MC MB-MC 00 ON Abnormal Closed Open Normal Open Closed OFF  Open Closed 01 (Default) ON Abnormal Open Closed Normal Closed Open OFF  Open Closed Resistance load Inductive load MA-MC Max. contact capacity 250 V AC, 2 A 30 V DC, 8 A 250 V AC, 0.2 A 30 V DC, 0.6 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA MB-MC Max.

contact capacity 250 V AC, 1 A 30 V DC, 1 A 250 V AC, 0.2 A 30 V DC, 0.2 A Min. contact capacity 100 V AC, 10 mA 5 V DC, 100 mA