omron — Frequency Arrival Signal

4-2 Function Mode Signal During RUN •While the Inverter is running, this signal is output via multi-function output terminals P1 to P5 or the relay output terminal. •Allocate "00" (RUN) to any of multi-function output terminals P1 to P5 (C021 to C025) or the relay output terminal (C026). •This signal is also output during DC injection braking. Below is the time chart. 4 Functions Frequency Arrival Signal •When the output frequency reaches the set level, a frequency arrival signal is output. •For elevating machines, use this signal for applying the brake. To release the brake, use the overtorque signal. •Allocate "01" (FA1: Constant speed arrival signal), "02" (FA2:

Set frequency exceeded), "06" (FA3: Set frequency only), "24" (FA4: Set frequency exceeded 2), or "25" (FA5: Set frequency only 2) to any of multi-function output terminals P1 to P5 (C021 to C025) or the relay output terminal (C026). •Below is the hysteresis of the frequency arrival signal: ON: (Set frequency - 1% of the maximum frequency) (Hz) OFF: (Set frequency - 2% of the maximum frequency) (Hz) If "06" (FA3) or "25" (FA5) is set, however, operation during acceleration is: ON: (Set frequency - 1% of the maximum frequency) (Hz) OFF: (Set frequency + 2% of the maximum frequency) (Hz) and operation during deceleration is: ON: (Set frequency + 1% of the maximum frequency) (Hz) OFF:

(Set frequency - 2% of the maximum frequency) (Hz) 4-94 Output frequency FW RUN Parameter No. Function name Data Default setting Unit C042 Arrival frequency during acceleration 0.0: Does not output arrival signal during acceleration. 0.1 to 400.0: Outputs arrival signal during acceleration. 0.0 Hz C045 Arrival frequency during acceleration 2 C043 Arrival frequency during deceleration 0.0: Does not output arrival signal during deceleration. 0.1 to 400.0: Outputs arrival signal during deceleration. 0.0 Hz C046 Arrival frequency during deceleration 2