omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-50 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Control parameter H030 Motor parameter R1 (auto-tuning data) 0.001 to 9.999 10.00 to 65.53 Depends on the motor capacity. No Ω 4-107 4-110 H230 * 2nd motor parameter R1 (auto-tuning data) Depends on the motor capacity. H031 Motor parameter R2 (auto-tuning data) 0.001 to 9.999 10.00 to 65.53 Depends on the motor capacity. No Ω H231 * 2nd motor parameter R2 (auto-tuning data) Depends on the motor capacity.

H032 Motor parameter L (auto-tuning data) 0.01 to 99.99 100.0 to 655.3 Depends on the motor capacity. No mH H232 * 2nd motor parameter L (auto-tuning data) Depends on the motor capacity. H033 Motor parameter Io (auto-tuning data) 0.01 to 99.99 100.0 to 655.3 Depends on the motor capacity. No A H233 * 2nd motor parameter Io (auto-tuning data) Depends on the motor capacity. H034 Motor parameter J (auto-tuning data) 0.001 to 9.999 10.00 to 99.99 100.0 to 999.9 1000. to 9999. Depends on the motor capacity. No kgm2 H234 * 2nd motor parameter J (auto-tuning data) Depends on the motor capacity.