Single-axis controllers General data and operating conditions 4 4.2 4.2 General data and operating conditions General data Conformity and approval Conformity Approval Design Housing Mounting clearances 4.2-1 EDS94SPP101 EN 3.1-04/2007 CE 73/23/EEC Low-Voltage Directive UL UL 508C Power Conversion Equipment, 1D74, File No. 132659 Protection of persons and devices Enclosure EN 60529 IP 20 Not in the wire range of the terminals on the motor side NEMA 250 Protection against contact to type 1 Insulation resistance EN 61800-5-1 Overvoltage category III Reduction from 2000 m amsl onwards:
Overvoltage category II Insulation of control circuits EN 61800-5-1 Safe mains isolation by double/reinforced insulation. Short-circuit strength EN 61800-5-1 Motor connection: with restrictions, fault acknowledgement required Control connections: without restrictions Motor protective measures against z Short circuit z Earth fault z Overvoltage z Motor stalling z Motor overtemperature (PTC or thermal contact, I2t monitoring) Discharge current EN 61800-5-1 > 3.5 mA AC, > 10 mA DC Observe regulations and safety instructions! Cyclic mains switching Cyclic mains switching of 5 times in 5 minutes is permissible without restrictions.
Carrier housing Carrier housing Device sizes 1, 2 and 3 Glass-fiber reinforced plastic Device sizes as of 6 Metal Dimensions see ”Mechanical installation” Weight see ”Mechanical installation” Mounting conditions Mounting place In the control cabinet Mounting position Vertical Above/below To the sides ≥80 mm / ≥120 mm Observe the device-related notes on mounting. Side-by-side mounting without any clearance