Single-axis controllers General data and operating conditions 4 4.2 Power systems Operating conditions Environmental conditions Climate Vibration resistance (9.81 m/s 2 = 1 g) General electrical data Motor cable requirements Capacitance per unit length Electric strength 4.2-2 EDS94SPP101 EN 3.1-04/2007 ”Single Drive” supply conditions AC-mains operation Direct connection DC-bus operation Direct connection via terminals or busbars(can be retrofitted) For more information, please see the chapter DC-bus operation. TT TN With grounded phase IT Operation permitted without restrictions. Operation with additional measures permitted:
z Protection of persons according to EN 61800-5-1 requires the supplementary insulation of the control cables. z Measures described for IT systems must be applied. Additional device-internal measure required Motors EN 60034 Only use motors suitable for inverter operation. Insulation resistance: max. û ≥1.5 kV, max. du/dt ≥5 kV/μs Storage Transport Operation IEC/EN 60721-3-1 1K3 (-25 ... +60 °C) IEC/EN 60721-3-2 2K3 (-25 ... +70 °C) IEC/EN 60721-3-3 3K3 (-10 ... +55 °C) Current derating at +45 ... +55 °C: 2.5 %/°C Site altitude 0 ... 4000 m amsl 1000 ... 4000 m amsl:
current derating of 5 %/1000 m Pollution EN 61800-5-1 Pollution degree 2 Transport Operation IEC/EN 60721-3-2 2M2 EN 61800-2 2 ... 9 Hz: amplitude 3.5 mm 10 ... 200 Hz: acceleration resistant up to 10 m/s2 200 ... 500 Hz: acceleration resistant up to 15 m/s2 Germanischer Lloyd 5 ... 13.2 Hz: amplitude ±1 mm 13.2 ... 100 Hz: acceleration resistant up to 0.7 g EN 50178 10 ... 57 Hz: amplitude 0.075 mm 57 ... 150 Hz: acceleration resistant up to 10 m/s2 ≤ 2.5 mm2/AWG 14 ≥ 4 mm2/AWG 12 CCore/core/CCore/shield CCore/core/CCore/shield VDE 0250-1 UL U0/U = 0.6/1.0 kV (U0 = r.m.s. value of external conductor to PE, U = r.m.s. value of external conductor to external conductor) U ≥600 V (U = r.m.s.
value of external conductor to external conductor)