Lenze — 4.2 General data and operating conditions

Single-axis controllers General data and operating conditions 4 4.2 Protective insulation  Danger! Operation of the controller on a phase earthed mains with a rated mains voltage of ≥ 400 V: ƒ The protection against accidental contact is not ensured without external measures. ƒ If protection against accidental contact acc. to EN 61800-5-1 is required for the control terminals of the controller and the terminals for the plugged-in device modules, – an additional basic insulation must be available. – the components to be connected must have the second basic insulation.  Danger!

Dangerous electrical voltage When one common voltage source is used for control voltages in separate potential areas, the protective insulation between the separate potential areas is deactivated. Possible consequences: ƒ The specified protective insulations are not complied with. Protective measures: ƒ Use independent voltage sources.  4.2-5 EDS94SPP101 EN 3.1-04/2007