A90 series Inverter User Guide 45 F00.28 Motor Parameter Group Options 0: Motor 1 Parameter 1: Motor 2 Parameter 0 〇 F00.29 User Password 0 - 65535 0 〇 F00.30 Inverter Type 0: Heavy duty 1: Normal duty 0 〇 F01 Motor 1 Parameter F01.00 Motor Type 0: Common Induction Motor 1: Variable speed Induction Motor 2:
Permanent Magnet Synchronous Motor 0 〇 F01.01 Motor Rated Power 0.10~650.00 kW Model related 〇 F01.02 Motor Rated Voltage 50~2000 V 〇 F01.03 Motor Rated Current 0.01 - 600.00 (Motor Rated Power ≤ 75 kW) 0.1 - 6000.0 (Motor Rated Power >75 kW) A 〇 F01.04 Motor Rated Frequency 0.01~600.00 Hz 〇 F01.05 Motor Rated Speed 1~60000 rpm 〇 F01.06 Motor Winding Connection 0:Y 1:Δ Model related 〇 F01.07 Motor Rated Power Factor 0.600~1.000 〇 F01.34 Motor Parameter Autotune 00: No Autotune 01: Stationary Autotune of Asynchronous motor 02: Rotational Autotune of Asynchronous motor 11: Stationary Autotune of Synchronous Motor 12:
Rotational Autotune of Synchronous Motor 00 〇 F02 Input Terminal Function Group F02.00 X1 Digital Input Function 0: No Function 1: Run Terminal “RUN” 2: Terminal R/F 3: 3-Wire Sequence Stop Control 4: Forward JOG (FJOG) 5: Reverse JOG (RJOG) 6: Terminal UP 7: Terminal DOWN 8: Clear UP/Down Offset 9: Coast to Stop 10: Fault Reset 11: Preset Speed Terminal 1 12: Preset Speed Terminal 2 13: Preset Speed Terminal 3 14: Preset Speed Terminal 4 The other options are shown in Table 9-2.
Digital Input Terminal Functions 1 〇 F02.01 X2 Digital Input Function 2 〇 F02.02 X3 Digital Input Function 11 〇 F02.03 X4 Digital Input Function 12 〇 F02.04 X5 Digital Input Function 13 〇 F02.05 X6 Digital Input Function 10 〇 F02.07 AI1 Digital Input Function 0 〇 F02.08 AI2 Digital Input Function 0 〇