A90 series Inverter User Guide 55 F08.05 Preset Speed 6 0.00 - Maximum Frequency F00.16 Hz 25.00 ● F08.06 Preset Speed 7 0.00 - Maximum Frequency F00.16 Hz 30.00 ● F08.07 Preset Speed 8 0.00 - Maximum Frequency F00.16 Hz 35.00 ● F08.08 Preset Speed 9 0.00 - Maximum Frequency F00.16 Hz 40.00 ● F08.09 Preset Speed 10 0.00 - Maximum Frequency F00.16 Hz 45.00 ● F08.10 Preset Speed 11 0.00 - Maximum Frequency F00.16 Hz 50.00 ● F08.11 Preset Speed 12 0.00 - Maximum Frequency F00.16 Hz 50.00 ● F08.12 Preset Speed 13 0.00 - Maximum Frequency F00.16 Hz 50.00 ● F08.13 Preset Speed 14 0.00 - Maximum Frequency F00.16 Hz 50.00 ● F08.14 Preset Speed 15 0.00 - Maximum Frequency F00.16 Hz 50.00 ● F08.15 Simple PLC Running Mode 0:
Stop after Single Running 1: Stop after given Times of Cycles 2. Run at Last Preset Speed after given Times of Cycles 3: Continuous Cycle 0 ● F08.16 Given Times of Cycles 1 - 10000 1 ● F08.17 Simple PLC Memory Ones Place: Stop Memory selection 0: Disabled (Start from Preset Speed 1) 1: Enabled (Start at last stop) Tens Place: Power Failure Memory 0: Disabled (Start from Preset Speed 1) 1: Enabled (Start at Power Failure) 0 ● F08.18 Simple PLC Time Unit 0: second 1: minute 0 ● F08.19 Setting of Preset Speed 1 Ones Place: Running Direction 0: Forward 1: Reverse Tens Place: Acceleration/Deceleration Time 0: Acceleration/Deceleration Time 1 1: Acceleration/Deceleration Time 2 2:
Acceleration/Deceleration Time 3 3: Acceleration/Deceleration Time 4 0 ● F08.20 Running Time of Preset Speed 1 0.0~6000.0 s/min 5.0 ● F08.21 Setting of Preset Speed 2 The parameter setting range is the same as F08.19 0 ● F08.22 Running Time of Preset Speed 2 0.0~6000.0 s/min 5.0 ● F08.23 Running Time of Preset Speed 3 The parameter setting range is the same as F08.19 0 ● F08.24 Running Time of Preset Speed 3 0.0~6000.0 s/min 5.0 ● F08.25 Setting of Preset Speed 4 The parameter setting range is the same as F08.19 0 ●