A90 series Inverter User Guide 58 F09.22 PID Feedback Filter Time 0.000 - 30.000 s 0.000 ● F09.23 PID Output Filter Time 0.000 - 30.000 s 0.000 ● F09.24 Upper Limit Detection Value of PID Feedback Disconnection 0.00 - 100.00 100.00=Feedback Disconnection Disabled % 100.00 ● F09.25 Lower Limit Detection Value of PID Feedback Disconnection 0.00 - 100.00 0.00=Feedback Disconnection Disabled % 0.00 ● F09.26 PID Feedback Disconnection Detection Time 0.000 - 30.000 s 0.000 ● F09.27 PID Sleep Control 0: Disabled 1: Enabled,0Hz running 2: Enabled, Lower Limit Frequency Running 3:
Enabled, Shutdown Output 0 ● F09.29 Sleep Delay Time 0.0~6500.0 s 0.0 ● F09.30 Wake up Action Point 0.00 - 100.00 (100.00 corresponds to F09.03) % 0.00 ● F09.31 Wake up Delay Time 0.0 - 6500.0 s 0.0 ● F09.32 Preset PID Setting 1 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.33 Preset PID Setting 2 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.34 Preset PID Setting 3 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.39 Wake up mode selection 0:Target pressure F09.01 * wake up coefficient 1:Wake up point (F09.30) 0 〇 F09.40 Wake up coefficient 0.0 -100.0 (100.0 corresponds to F09.01) % 90.0 F09.41 Pipeline overpressure alarm pressure 0.0 ~ pressure sensor range F09.03 bar 6.0 ● F09.42 Overpressure protection delay time 0 ~ 3600 (0 :
invalid) s 3 ● F10 Communication Function Group F10.00 Inverter Address 1 - 247, 0 as broadcasting address 1 〇 F10.01 Modbus Communication Baud Rate 0:4800 1:9600 2:19200 3:38400 4:57600 5:115200 1 〇