User Manual of A90 Series Inverter The real-time status of the current virtual terminal is displayed. 7.18 Monitoring Parameter Group of F18 Group This group of parameters is used only to view the current status of the inverter and cannot be changed. 245 terminal status 0: Invalid 1: valid 00000 F17.38 Virtual output terminal status VY8 VY7 VY6 VY5 VY4 VY3 VY2 VY1 000 00000 × 0: Invalid 1: valid Function Function code Parameter description Unit code name F18.00 Output frequency Display the current output frequency of the inverter. Scope: 0.00 to upper frequency limit. ★: This parameter will be updated promptly in the speed control mode.
Hz F18.01 Set frequency Display the current set frequency of the inverter. Scope: 0.00 to maximum frequency F00.16. ★: This parameter will be updated promptly in the speed control mode. Hz F18.02 Reserved F18.03 Estimate feedback frequency Display the estimated feedback frequency in the SVC control mode. Scope: 0.00 to upper frequency limit. ★: This parameter will be updated promptly in the SVC control mode. Hz F18.04 Output torque Display the current output torque of the inverter. Scope: -200.0 - 200.0. % F18.05 Torque setting Display the current set torque of the inverter. Scope: -200.0 - 200.0. ★: This parameter will be updated promptly in the torque control mode.
% F18.06 Output current Display the current output current of the inverter. Depending on the rated power level of the motor, the range is as follows: 0.00 to 650.00 (rated power of motor: ≤ 75 kW) 0.0 to 6500.0 (rated power of motor: > 75 kW) A F18.07 Output current percentage Display the current output current as a percentage (relative to the rated current of the inverter). Range: 0.0 to 300.0. % F18.08 Output voltage Display the current output voltage of the inverter. Scope: 0.0 - 690.0. V