User Manual of A90 Series Inverter When the inverter has an aforesaid fault, press the STOP/RESET key STOP RESET to for resetting/clearing or use the fault resetting terminal to exit the fault status. If the fault has been eliminated, the inverter will return to the function setting status; otherwise, the digital tube will continue to display the current fault information. The following numbers are used to read the fault type through communication: E11 and subsequent faults are represented by the numbers behind the letter “E”. For example, “E11” corresponds to the number “11”. Comparison table of English uppercase display: Comparison table of digital font display:
259 properly during parameter identification. 3. The motor is not connected. 4. The rotary self-learning motor is not disconnected from the load. 5. The motor fails. 3. Check the connection between the inverter and motor. 4. Disconnect the rotary self-learning motor from the load. 5. Check the motor. E26 Load loss protection 1. The motor is not connected or does not match the load. 2. Load loss occurs. 3. The parameters of load loss protection are not set reasonably. 1. Check the wiring and use the appropriate motor 2. Check the equipment. 3. Change the off-load detection level F07.22 and detection time F07.23. E27 Up to cumulative power-on time The inverter maintenance time is up.
Contact the dealer for technical support. E28 Up to cumulative running time The inverter maintenance time is up. Contact the dealer for technical support. 0 E01 E02 E03 E04 E05 E06 E07 E08 E09 E10 0 1 2 3 4 5 6 7 8 9 10 a b c d e f g h i l A B C D E F G H I L n o p q r s t u x y N O P Q R S T U X Y 1 2 3 4 5 6 7 8 9 0